Plan Review Notes
Plan Review Notes For Permit 01030614
Permit Number 01030614
Review Stop B
Sequence Number 3
Notes
Date Text
2001-08-23 00:00:00RE: 7/21/01 LETTER FROM R. KUPI.SEE
 SBC 504 FOR BUILDINGS LOCATED ON THE
 SAME PROPERTY AND THE REQUIREMENT FOR
 ASSUMED PROPERTY LINES.NOTE YOUR
 ASSUMED PROPERTY LINE AND THEN APPLY
 TABLE 600 REQUIREMENTS.
  
 F102.2.5 IS APPLICABLE SINCE THE
 TOWNHOUSE WALL IS EFFECTIVELY A ZERO
 LOT LINE AND NOT 30'FURTHER THE 13D
 SPRINKLER IS NOT CONSIDERED AS AN
 EXCEPTION.SEE SBC 903.2.