| Notes |
| Date |
Text |
| 2001-07-19 00:00:00 | PLUMBING PLAN REVIEW,DENIED. | | | (1) PREVIOUS COMMENTS DATED 04-26-01, | | | SHT P-1 NOTE (14) AND P-2 THRU P-10, | | | WATER HAMMER ARRESTORS TO BE INSTALLED | | | AS PER MANFACTURE INSTRUTIONS,NOT AT THE | | | HIGH POINT.USE WATER HAMMER ARRESTOR | | | STD PDI-201 FOR SIZE AND PLACEMENT. | | | (2A) SHT A-62, CABANA REST RM'S,PALM BCH | | | CNTY HEALTH DEPT, PLAN REVEIEW AND | | | COMMMENTS PRIOR TO PLUMBING PLAN REVIEW. | | | (2B) COMPLY W/FACBC SEC 4.1.2(2) ACCESS- | | | IBLE SITE AND EXTERIOR FACILITIES. | | | SEC 4.2.2.1 DOOR'S, CLEAR FLR SPACE,W/C. | | | (3) IRRIGATION PLANS & LOCATION OF BACK | | | FLOW PREVENTER. | | | END OF COMMENTS PAUL CHMITZ | | | QUESTIONS561-659-8096X8233 |
|