| Plan Review Notes For Permit 01030614 |
| Permit Number |
01030614 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-07-23 00:00:00 | *******************PROVISO************** | | | | | | | | | FIRE DAMPERS SHALL COMPLY WITH UL 555 | | | AND SHALL BEAR THE LABEL OF ANY | | | APPROVED TESTING AGENCY. | | | | | | NOTE:PLANS DO NOT INDICATE MEANS OF | | | VENTILATION FOR THE CABANAS AT | | | THE POOL.PLEASE SUBMIT EXHAUST | | | FANS AND HOW AIR MAKE-UP WILL BE | | | MAINTAINED. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|