Plan Review Notes
Plan Review Notes For Permit 01030614
Permit Number 01030614
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2001-07-05 00:00:00IT APPEARS THAT ALL PREVIOUS COMMENTS
 BY THE FIRE RESCUE DEPARTMENT HAS
 BEEN MITIGATED.
  
 1) PLEASE CLARIFY IN WRITING TO THIS
 OFFICE IF INDIVIDUAL FIRE DEPARTMENT
 CONNECTIONS WILL BE PROVIDED. PLANS
 SEEM TO SUGGEST INDIVIDUAL ONES AND
 COMMON ONES FOR THE BUILDINGS OR UNITS.
 2) COULD NOT LOCATE FIRE SPRINKLER
 MONITORING DEVICES FOR EACH BUILDING.
 3) PLEASE BE ADVISED THAT CITY CODE
 SECTION 11-4 REQUIRES THAT NO DEVICES
 BE PLACED WITHIN 18 FEET OF FIRE
 HYDRANTS.
 4) ALSO PLEASE BE ADVISED THAT THE
 PROPERTY APPEARS TO BE LOCATED IN THE
 CITY FIRE LIMITS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910