| Plan Review Notes For Permit 01030614 |
| Permit Number |
01030614 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-07-20 00:00:00 | REVIEW FOR TABLE 600 IS APPLIED TO EACH | | | BLDG, (TOWNHOUSE UNIT) ON A PER FLOOR | | | BASIS USING THE HEIGHT BETWEEN FLOOR | | | AND CEILING TO DETERMINE AREA. | | | | | | THE FIRST FLOOR GARAGE DOOR OPENINGS | | | WILL EXCEED THE ALLOWABLE 40% OPEN | | | AREA.SBC 705.1.1.2 REQUIRES OPENINGS | | | WITHIN 15' OF A PROPERTY LINE TO BE | | | PROTECTED.BUILDINGS C, D & F WILL BE | | | LOCATED WITHIN THE FIRE DISTRICT AND | | | MUST BE A MINIMUM TYPE V CONSTRUCTION | | | AND WILL NEED PROTECTED OPENINGS. | | | BUILDINGS A, B & E WILL FALL OUTSIDE | | | THE FIRE DISTRICT AND CAN BE VIEWED AS | | | TYPE VI AND HAVE NON FIRE RATED | | | OPENINGS.ALL MUST MEET THE PERCENTAGE | | | OF AREA ALLOWED. | | | | | | THE FIRE DISTRICT FOR THIS PROPERTY | | | FORMS A LINE APPROXIMATELY 140' EAST OF | | | THE CENTERLINE OF DIXIE AND 140' NORTH | | | OF TH | | | E CENTERLINE OF FLAMINGO. | | | | | | SOME OF THE PRODUCT REPORTS PROVIDED ARE | | | ILLEGIBLE OR EXPIRED. |
|