2001-07-20 00:00:00REVIEW FOR TABLE 600 IS APPLIED TO EACH
 BLDG, (TOWNHOUSE UNIT) ON A PER FLOOR
 BASIS USING THE HEIGHT BETWEEN FLOOR
 AND CEILING TO DETERMINE AREA.
  
 THE FIRST FLOOR GARAGE DOOR OPENINGS
 WILL EXCEED THE ALLOWABLE 40% OPEN
 AREA.SBC 705.1.1.2 REQUIRES OPENINGS
 WITHIN 15' OF A PROPERTY LINE TO BE
 PROTECTED.BUILDINGS C, D & F WILL BE
 LOCATED WITHIN THE FIRE DISTRICT AND
 MUST BE A MINIMUM TYPE V CONSTRUCTION
 AND WILL NEED PROTECTED OPENINGS.
 BUILDINGS A, B & E WILL FALL OUTSIDE
 THE FIRE DISTRICT AND CAN BE VIEWED AS
 TYPE VI AND HAVE NON FIRE RATED
 OPENINGS.ALL MUST MEET THE PERCENTAGE
 OF AREA ALLOWED.
  
 THE FIRE DISTRICT FOR THIS PROPERTY
 FORMS A LINE APPROXIMATELY 140' EAST OF
 THE CENTERLINE OF DIXIE AND 140' NORTH
 OF TH
 E CENTERLINE OF FLAMINGO.
  
 SOME OF THE PRODUCT REPORTS PROVIDED ARE
 ILLEGIBLE OR EXPIRED.