| 2001-04-26 00:00:00 | PLUMBING PLAN REVIEW. SPC-94 | | | | | | FAILED | | | | | | (1) TYPICAL WATER RISER DIAGRAMS. AIR- | | | CHAMBERS TO COMPLY WITH 607.8.3 AND | | | BE ACCESSABLE AND RECHARGEABLE. | | | | | | (2) PAGE P.2 WHERE DOES THE VENT FROM | | | THE POWDER ROOM TERMINATE? | | | | | | (3) CIVIL PLANS WITH SITE SEWER, WATER, | | | ECT. NOT INCLUDED WITH PLANS AS | | | INDICATED ON SHEET SCHEDULE. | | | | | | REVIEW BY KEN STEVENS. (561) 659-8096 | | | EXT. 8377 |
|