| 2001-04-19 00:00:00 | *******************DENIED*************** |
| | |
| | |
| | APARTMENTS: |
| | |
| | 1.DRYER VENTS SHALL NOT EXCEED 25' |
| | FROM DRYER LOCATION TO WALL OR CAP. |
| | THERE WILL BE A 2 1/2 FT DEDUCTION |
| | FOR EVERY 45 DEGREE OFFSET & A 5 FT |
| | DEDUCTION FOR EVERY 90 DEGREE OFF- |
| | SET.1997 SMC 509.3. |
| | |
| | 2.EXHAUST DUCTS FOR DRYERS SHALL |
| | COMPLY WITH 1997 SMC 509.1, FOR |
| | THE ASSEMBLY/CONTRUCTION OF EXHAUST |
| | DUCT.PLEASE INDICATE ANY ACCESS |
| | DOORS OR METHOD USED TO CLEAN LINT |
| | FROM DUCT. |
| | |
| | 3.PLEASE INDICATE ON PLAN WHICH A/C |
| | UNIT GOES TO WHICH APARTMENT. |
| | |
| | 4.PLAN INDICATES A SUPPLY DUCT |
| | DROPING INTO GARAGE AREA TO SUPPLY |
| | THE FIRST FLOOR. WHERE THE DUCT |
| | PENETRATES THE WALL FROM THE GARAGE |
| | INTO THE BATHROOM WILL REQUIRE A |
| | FIRE DAMPER IF THIS IS A RATED WALL |
| | (SEE DRAWING A.9 & AC.1, 1ST FLOOR) |
| | PLEASE PROVIDE MANUFACTURE SPECS |
| | AND MOUNTING DETAILS FOR ANY FIRE |
| | DAMPERS.FIRE DAMPERS MUST BE |
| | IDENTIFIED ON PLAN. |
| | |
| | 5.DRAWING AC.10, DETAIL FOR SUSPENDED |
| | A/C UNIT & AUX. DRAIN PAN DETAIL, |
| | SPECIFY WHERE THE AUXILIARY DRAIN |
| | WILL TERMINATE.SHALL COMPLY WITH |
| | 1997 SMC 304.8.6.1, SEPERATE DRAIN |
| | SHALL BE EXTENDED FROM PAN AND |
| | TERMINATING AT A CONSPICUOUS POINT |
| | TO SERVE AS AN ALARM THAT REGULAR |
| | DRAIN IS RESTRICTED. A FLOAT SWITCH |
| | IN LIEU OF DRAIN LINE MAY BE USED. |
| | |
| | 6.AHU'S SHALL COMPLY WITH 1997 SMC |
| | 304.4.2, IN ATTIC A LIGHT SHALL BE |
| | ON THE SERVICE SIDE OF EQUIPMENT |
| | WHICH IS CONTROLLED BY A SWITCH |
| | LOCATED AT THE ACCESS OPENING. |
| | |
| | 7.CONDENSER UNITS SHALL COMPLY WITH |
| | 1997 SMC 304.7.2, A MINIMUM OF 30" |
| | OF CLEAR SPACE ON THE SERVICE SIDE |
| | FOR INSPECTION AND SERVICING. |