| Date |
Text |
| 2001-03-27 00:00:00 | 1) WRONG BUILDING CODE EDITION |
| | REFERENCED. SHOULD READ 1997 EDITION |
| | INSTEAD OF 1994. |
| | 2) FIRE HYDRANTS NOT SHOWN ON SITE PLAN. |
| | 3) BUILDING ADDRESSES NOT SHOWN ON |
| | ELEVATION DRAWINGS. BUILDING ADDRESSES |
| | TO COMPLY WITH CITY CODE REQUIREMENTS. |
| | 4) HOW IS COMBUSTIBLE LINT REMOVED FROM |
| | THE INDIVIDUAL DRYER VENT PIPES. |
| | 5) NO FIRE SPRINKLER DRAWINGS OR |
| | HYDRAULIC CALCULATIONS PROVIDED WITH |
| | DRAWINGS. PLEASE BE ADVISED THAT FS |
| | 553.895 (2) REQUIRES ALL NEW BUILDINGS |
| | THREE OR MORE STORIES IN HEIGHT |
| | REGARDLESS OF OCCUPANCY TO BE PROTECTED |
| | BY AN AUTOMATIC FIRE SPRINKLER SYSTEM. |
| | 6) THE REQUIRED FIRE SPRINKLER SYSTEM(S) |
| | ARE TO BE MONITORED BY A LICENSED UL |
| | LISTED CENTRAL STATION APPROVED BY THE |
| | FIRE RESCUE DEPARTMENT. THE MONITORING |
| | REQUIREMENT IS BOTH BY BUILDING AND FIRE |
| | CODE REGULATIONS. |
| | 7) PLEASE PROVIDE INTERIOR FINISH |
| | CLASSIFICATION INFORMATION FOR UNITS. |
| | 8) PLEASE PROVIDE FLAME SPREAD |
| | INFORMATION FOR CEDAR SHAKES PLANNED FOR |
| | USE. |
| | 9) EACH INDIVIDUAL UNIT TO COMPLY WITH |
| | ONE AND TWO FAMILY DWELLINGS PER THE |
| | LIFE SAFETY CODE 1985 EDITION IF THEY |
| | PLATTED INDIVIDUALLY. IF THEY ARE NOT |
| | PLATTED INDIVIDUALLY, THEN THE |
| | REQUIREMENTS FOR NEW APARTMENTS PER THE |
| | LIFE SAFETY CODE 1985 EDITION ARE |
| | APPLICABLE. |
| | |
| | CAPTAIN MIKE CARSILLO |
| | 659-8096,EXT.8497 |
| | 835-2910 |