Notes
Date Text
2001-03-27 00:00:001) WRONG BUILDING CODE EDITION
 REFERENCED. SHOULD READ 1997 EDITION
 INSTEAD OF 1994.
 2) FIRE HYDRANTS NOT SHOWN ON SITE PLAN.
 3) BUILDING ADDRESSES NOT SHOWN ON
 ELEVATION DRAWINGS. BUILDING ADDRESSES
 TO COMPLY WITH CITY CODE REQUIREMENTS.
 4) HOW IS COMBUSTIBLE LINT REMOVED FROM
 THE INDIVIDUAL DRYER VENT PIPES.
 5) NO FIRE SPRINKLER DRAWINGS OR
 HYDRAULIC CALCULATIONS PROVIDED WITH
 DRAWINGS. PLEASE BE ADVISED THAT FS
 553.895 (2) REQUIRES ALL NEW BUILDINGS
 THREE OR MORE STORIES IN HEIGHT
 REGARDLESS OF OCCUPANCY TO BE PROTECTED
 BY AN AUTOMATIC FIRE SPRINKLER SYSTEM.
 6) THE REQUIRED FIRE SPRINKLER SYSTEM(S)
 ARE TO BE MONITORED BY A LICENSED UL
 LISTED CENTRAL STATION APPROVED BY THE
 FIRE RESCUE DEPARTMENT. THE MONITORING
 REQUIREMENT IS BOTH BY BUILDING AND FIRE
 CODE REGULATIONS.
 7) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR UNITS.
 8) PLEASE PROVIDE FLAME SPREAD
 INFORMATION FOR CEDAR SHAKES PLANNED FOR
 USE.
 9) EACH INDIVIDUAL UNIT TO COMPLY WITH
 ONE AND TWO FAMILY DWELLINGS PER THE
 LIFE SAFETY CODE 1985 EDITION IF THEY
 PLATTED INDIVIDUALLY. IF THEY ARE NOT
 PLATTED INDIVIDUALLY, THEN THE
 REQUIREMENTS FOR NEW APARTMENTS PER THE
 LIFE SAFETY CODE 1985 EDITION ARE
 APPLICABLE.
  