| 2001-04-06 00:00:00 | ****************UNSAT *************** | | | | | | 1)NOTE: PLEASE NOTE THAT PLANS SHOW NO | | | MAINS FOR PANELS OF EACH UNIT? SHOWS | | | MLOMAINS REQ`D PER 225-31 | | | | | | 2)NOTE: PLEASE NOTE MISSING OUTLETS IN | | | SOME UNITS REQ`D BY 210-52 | | | | | | 3)NOTE: PLEASE NOTE THE EQUIPMENT | | | GROUNDING CONDUCTOR SHOWN BETWEEN | | | METERCAN AND PANEL. EQUIPMENT GROUND IS | | | ONLY INSTALLED AFTER THE FIRST MEANS OF | | | DISCONNECT. INSTALLATION SHOWS NEUTRAL | | | BEING PARALLED. | | | | | | 4)NOTE: PLANS ARE MISSING DETAIL FOR | | | FEEDS TO ALL HOUSE PANELS. WIRE,METERS | | | CONDUITS,,,ETC. PLEASE SHOW LOCATIONS | | | OF ALL ON PLAN. GROUNDING DETAIL PER | | | 250-50 | | | | | | 5)NOTE: PLEASE NOTE THAT ALL THE HEIGHT | | | REQUIREMENTS FOR DEVICES NEED TO BE | | | SHOWN ON PLANS PER F.H.A.R. 24CFR | | | 100.205 | | | PLEASE MAKE NOTE ON EACH SHEET FOR | | | SEPARATE UNITS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS , | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|