Plan Review Notes
Plan Review Notes For Permit 01030614
Permit Number 01030614
Review Stop E
Sequence Number 1
Notes
Date Text
2001-04-06 00:00:00****************UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT PLANS SHOW NO
 MAINS FOR PANELS OF EACH UNIT? SHOWS
 MLOMAINS REQ`D PER 225-31
  
 2)NOTE: PLEASE NOTE MISSING OUTLETS IN
 SOME UNITS REQ`D BY 210-52
  
 3)NOTE: PLEASE NOTE THE EQUIPMENT
 GROUNDING CONDUCTOR SHOWN BETWEEN
 METERCAN AND PANEL. EQUIPMENT GROUND IS
 ONLY INSTALLED AFTER THE FIRST MEANS OF
 DISCONNECT. INSTALLATION SHOWS NEUTRAL
 BEING PARALLED.
  
 4)NOTE: PLANS ARE MISSING DETAIL FOR
 FEEDS TO ALL HOUSE PANELS. WIRE,METERS
 CONDUITS,,,ETC. PLEASE SHOW LOCATIONS
 OF ALL ON PLAN. GROUNDING DETAIL PER
 250-50
  
 5)NOTE: PLEASE NOTE THAT ALL THE HEIGHT
 REQUIREMENTS FOR DEVICES NEED TO BE
 SHOWN ON PLANS PER F.H.A.R. 24CFR
 100.205
 PLEASE MAKE NOTE ON EACH SHEET FOR
 SEPARATE UNITS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS ,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372