| Plan Review Notes For Permit 01030614 |
| Permit Number |
01030614 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-04-17 00:00:00 | 1 IMPACT FEES MUST BE PAID TO PALM BEACH | | | COUNTY.CALL 233-5025 FOR MORE | | | INFORMATION. | | | | | | 2A RESIDENT INSPECTOR IS REQUIRED FOR | | | THIS TYPE OF PROJECT.CALL DON NEELY | | | FOR MORE INFORMATION.659-8096 X 8333. | | | | | | 3 THE CITY USES THE 1997 STANDARD CODES | | | TH THE EXCEPTION OF THE 1994 PLUMBING | | | CODE. | | | | | | 4SHOW THE FREE AREA OF THE 1 INCH | | | SCREEN FOR THE SOFFIT VENT CALCULATIONS | | | SHOWN ON SHEET A3. | | | | | | 5THE TWO HOUR PARTY WALLS MUST PROJECT | | | 18" BEYOND THE COMBUSTIBLE VENER ON THE | | | EXTERIOR WALSS.SEE SBC 704.5.1.2. | | | | | | 6PLEASE PROVIDE THE TEST DATA FOR THE | | | WINDOWS, DOORS AND ROOF COVERINGS.SEE | | | SBC 104.2. | | | | | | 7SHOW HOW THE GLAZED OPENINGS WILL | | | COMPLY WITH THE CITY'S HURRICANE | | | MISSILE IMPACT RESISTANCE POLICY. | | | | | | 8SHOW THE TERMITE TREATMENT | | | SPECIFICATION FOR THE SOIL UNDER THE | | | BUILDINGS.SBC 2304. | | | | | | 9THE BUILDINGS FACING EACH OTHER MUST | | | COMPLY WITH SBC TABLE 600 AS TO THE | | | PERCENTAGE OF WALL AREA THAT MAY HAVE | | | OPENINGS. | | | | | | 10THE FIRE SPRINKLER DEWSIGN MUST BE | | | INCLUDED WITH THE PERMIT PLANS.FS | | | 553.79(2). |
|