| 2001-04-02 00:00:00 | ***************** UNSAT *************** | | | | | | 1)NOTE: BRANCH CIRCUIT #`S ARE NOT SHOWN | | | ON PLANS. PLEASE SUBMIT A PANEL | | | SCHEDULE TO CORRELATEWITH BRANCH | | | CIRUCIT #`S. | | | | | | 2)NOTE:PLEASE CLARIFY WHERE CONTINUOUS | | | LOADS ARE SHOWN AT 125%. CALCS SHOW | | | CONTINUOUS LOAD BUT, NOT AT 125%. | | | | | | 3)NOTE: PLEASE "J" BOX SHOWN IN STORAGE | | | AREA. NEEDS LIGHT FIXTURE SHOWN. | | | | | | 4)NOTE: PLEASE NOTE THAT DISCONNECTS | | | NEED TO BE SHOWN FOR A/C EQUIPMENT PER | | | 440-11. | | | | | | 5)NOTE: PLEASE NOTE THAT NO SERVICE | | | RISERDIAGRAM WAS SUBMITTED. | | | | | | 6)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 7)NOTE: PLEASE NOTE LOAD CALCULATIONS | | | NEED TO SHOWN FOR TRACK LIGHTING PER | | | 220-12. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | 561-659-8096 EXT 8372 |
|