Plan Review Notes
Plan Review Notes For Permit 01030582
Permit Number 01030582
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2001-06-07 00:00:001) THIS OFFICE HAS IDENTIFIED THE
 BUILDING AS A HIGH-HAZARD OCCUPANCY
 AND WILL REQUIRE SOME TYPE OF APPROVED
 FIRE SUPPRESSION SYSTEM FOR THE
 AREA CONTAINING THE METHANOL STORAGE.
 2) PLEASE PROVIDE APPROVALS FOR THE
 STORAGE TANKS.
 3) PLEASE INDICATE THE TYPES OF PRESSURE
 OF THE MATERIALS STORED IN THE TANKS.
 4) PLEASE INDICATE COMPLIANCE WITH CITY
 CODE SECTION 11, WHICH REQUIRES AT LEAST
 A 2" VENT PIPE FOR THE METHANOL STORAGE.
 5) PLEASE SHOW LOCATIONS OF ALL FIRE
 HYDRANTS, FIRE EXTINGUISHING EQUIPMENT
 AND FIRE PROTECTION FEATURES.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910