| 2001-06-06 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT # 01030582 |
| | 4325 N HAVERHILL RD |
| | WASTE WATER TREATMENT PLANT |
| | UNITED ENGINEERING CORP. |
| | PHONE #(305)994-7360 |
| | CAMP DRESSER & MC KEE |
| | PHONE #(561)689-3336 |
| | |
| | 1)- SBC 308.1 HAZARDOUS OCCUPANCY |
| | SUB-CLASSIFICATION : |
| | H-2; METHANOL MSDS METYAL ALCOHOL |
| | FLASH POINT: 12C |
| | H-4; CAUSTIC MSDS CAUSTIC SODA/ |
| | SODIUM HYDROXIDE |
| | 2)- SBC TABLE 308.B LIMITS TO 60 GAL. |
| | NOT SPRINKLERED FOR A CLASS 1A |
| | FLAMMABLELIQUID (METHAL ALCOHOL) |
| | FLAMMABLE & COMBUSTIBLE LIQUIDS IN OPEN |
| | CONTAINERS OR |
| | PRESSURIZED AT MORE THAN 15 PSIG. |
| | SBCTABLE 308.D CORROSIVES UNPROTECTED |
| | BY SPRINKLERS OR CABINET FOR SOLIDS |
| | 5,000LBS. LIQUIDS 500 GAL. IS THIS TYPE |
| | OF USAGE A SOLID OR LIQUID? |
| | 3)- SBC INDOOR STORAGE AREAS, STORAAGE |
| | BUILDINGS, AND AREAS OR ROOMS IN WHICH |
| | HAZARDOUS MATERIALS ARE DISPENSED OR |
| | USED SHALL BE PROTECTED BY AN AUTOMATIC |
| | SPRINKLER SYSTEM. HIGHER AUTOMATIC |
| | SPRINKLER DISCHARGE DENSITY MAY BE |
| | REQUIRED |
| | THAN REQUIRED THAN ARE SUPPLIED BY |
| | ORDINARY HAZARD, GROUP 2 TO ADEQUUATELY |
| | PRO- TECT MANY TYPES OF HAZARDOUS |
| | MATERIALS. NFPA 13, 1-1 INDICATES THAT |
| | THE PROTEC- |
| | TION OF MANY OF THESE MATERIALS IS BE- |
| | YOND THE SCOPE OF THE STANDARD. THERE- |
| | FORE, OTHER NFPA STANDARDS OR TEST DATA |
| | MAYBE SUBSTANTIATE SPRINKLER DESIGN |
| | DETAILS. |
| | 4)- SBC 407.2.1- STORAGE & DISPENSING |
| | AREAS- THIS DIVISION SHALL APPLY TO THE |
| | STORAGE AND DISPENSING OF HAZARDOUS MATE |
| | RIALS IN EXCESS OF THE EXEMPT AMOUNTS |
| | SPECIFIED IN TABLES 308.2A THROUGH |
| | 308.2D. |
| | 5)- SBC 407 2.3.4(3) SECONDARY CONTAIN- |
| | MENT SHALL BE DESIGNED TO RETAIN THE |
| | SPILL FROM THE LARGEST SINGLE CONTAINER |
| | PLUS THE DESIGN FLOW RATE OF THE AUTOMA- |
| | TIC FIRE EXTINGUISHING SYSTEM FOR THE |
| | AREA OF THE ROOM OR AREA IN WHICH THE |
| | STORAGE, WHICHEVER IS SMALLER. THE |
| | CONTAINMENT CAPACITY SHALL BE CAPABLE OF |
| | CONTAINING THE FLOW FOR A PERIOD OF 20 |
| | MINUTES. |
| | 6)- THE PRE-ENGINEERED METAL BUILDING |
| | HOUSING THE CHEMICALS WILL NEED TO |
| | SUPPLY SIGNED & SEALED ENGINEERED DRAW- |
| | INGS BEFORE THE ISSUANCE OF THE PERMIT, |
| | OR IT MAY BE BROUGHT IN UNDER SEPERATE |
| | PERMIT WITH ADDITIONAL FEES. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | (561) 659-8096 EX 8412 |