| 2001-04-12 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01030582 | | | 4325 N HAVERHILL RD | | | EAST CENTRAL REGIONAL | | | WASTE WATER TREATMENT PLANT | | | UNITED ENGINEERING CORP. | | | (305) 994-7360 | | | | | | 1)- SBC 704 SPECIAL HAZARD OCCUPANCIES | | | 407.1.1.1. STORAGE, DISPENSING, HANDLING | | | AND THE USE OF SOLID,LIQUID & GASEOUS | | | HAZARDOUS MATERIALS SHALL BE IN ACCORD- | | | ANCE WITH THIS SECTION & THE STANDARD | | | FIRE PREVENTION CODE. | | | | | | HAZARDOUS OCCUPANCY | | | H2: CLASS I,II,ORIII-A FLAMMABLES OR | | | COMBUSTIBLE LIQUIDS. | | | H4:HEALTH HAZARDS, CORROSIVES,IRRITANTS. | | | | | | 2)- SBC 407.1.3 REQUIRES AN AUTOMATIC | | | PROTECTION SYSTEM. | | | | | | 3)- SBC 407 2.3.4.(1-4) SHOW COMPLIANCE | | | WITH THESE SYSTEMS. | | | | | | 4)- SBC 104.2.2. ADDITIONAL INFORMATION | | | REQUIRED, PLEASE PROVIDE INFORMATION ON | | | THE STORAGE TANKS, THE SECONDARY CONTAIN | | | MENT SYSTEM, IS THERE A MEMBRANE APPLIED | | | TO THE CONTAINMENT AREA? IS THERE A | | | DRAIN? ETC? | | | | | | 5)- THE OPEN STRUCTURE ABOVE, WILL THERE | | | BE A CORROSIVE PROBLEM WITH THE CONTENTS | | | OF THE TANKS? SULFURIC ACID/ FERRIC SUL- | | | FATE? | | | | | | 6)- THE PRE-ENGINEERED METAL BUILDING | | | HOUSING THE CHEMICALS WILL NEED TO SUP- | | | PLY SIGNED & SEALED ENGINEERED DRAWINGS | | | BEFORE THE ISSUANCE OF THE PERMIT OR IT | | | MAY BE BROUGHT IN UNDER SEPERATE PERMIT | | | WITH ADDITIONAL FEES. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 EX 8412 |
|