| Notes |
| Date |
Text |
| 2001-03-20 00:00:00 | ******************DENIED**************** | | | | | | PROVIDE OUTSIDE AIR CALCULATIONS AND AIR | | | BALANCE SCHEDULE AS PER ASHRAE 62-89. | | | | | | DRAWING M1.1 DETAIL OF ROOF PLAN HVAC | | | INDICATES THE STAND FOR ACCU-1 HAVING A | | | MINIMUM HEIGHT OF 12" (NOTE 3), THIS | | | SHOULD BE A MINIMUM OF 18" FROM THE | | | ROOF SURFACE TO BOTTOM OF THE LOWEST | | | SUPPORT ON THE STAND.AMENDED 1997 SMC | | | 304.2.5. |
|