| 2001-03-16 00:00:00 | 1) CANVAS CANOPY TO BE FIRE RETARDANT. | | | 2) FIRE SPRINKLER HEADS SHOWN ON | | | REFLECTED CEILING PLAN ARE TO BE DONE | | | BY SEPARATE PLAN AND PERMIT. | | | 3) NO FIRE ALARM EQUIPMENT SHOWN ON | | | DRAWINGS. THE GENERAL NOTES ON A-3 | | | INDICATES AND ADT FIRE ALARM SYSTEM. | | | PLEASE CHECK CITY PLACE STANDARDS FOR | | | FIRE ALARM EQUIPMENT AND SYSTEMS. | | | 4) WRONG TRAVEL DISTANCE NOTED ON PLANS. | | | SHOULD READ 150 FEET INSTEAD OF 250 | | | FEET. |
|