| 2001-03-26 00:00:00 | **************** UNSAT **************** |
| | |
| | 1) NOTE: PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S) PER 210-11-C-3. |
| | MUST BE 20A AND #12AWG. |
| | |
| | 2)(NOTE: PLEASE SHOW GROUNDING |
| | ELECTRODEGOING TO BUILDING STEEL AND |
| | COLD WATER |
| | PER 250-50 |
| | |
| | 3)NOTE: PLEASE NOTE SERVICE ENTRANCE |
| | CONDUCTORS SHOWN AT 3-00`S "THIN". |
| | SHOWN FROM METER TO PANEL? PLEASE |
| | CLARIFY THIS SIZE AND INSULATION TYPE.?? |
| | |
| | 4)NOTE: PLEASE SEE ELECTRICAL NOTES<< |
| | "C" CONDUIT SIZE?, "D" SUB-PANEL CALCS?? |
| | |
| | 5) NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| | DWELLING UNIT. ROOMS WITH BATHS AND OR |
| | CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| | PER NFPA-72 2-2.1.1.1. |
| | |
| | 6) PLEASE NOTE MISSING OUTLET(S) REQ`D |
| | BY 210-52E OF THE NEC. |
| | |
| | 7) NOTE: PLEASE SHOW ALL OUTLET SPACING |
| | TO MEET 2`,6`,12` RULE PER 210-52. |
| | |
| | 8)NOTE: PLEASE SEE RISER DIAGRAM,, PLEAS |
| | E CLARIFYNOTE SHOWING2-#3`S,1-#2 IN |
| | 1/2" CONDUIT. FIRST CONDUIT IS WAY TOO |
| | SMALL AND WHAT DOES THIS GO TO. |
| | |
| | 9)NOTE: PLEASE SHOW SERVICE ENTRANCE |
| | CONDUCTORS ON RISER. |
| | |
| | PLEASE CLARIFY AND SUBMIT ALL THE ABOVE |
| | INFORMATION FOR REVIEW. IF THERE ARE |
| | ANY QUESTIONS PLEASE CALL. |
| | |