2001-03-26 00:00:00**************** UNSAT ****************
  
 1) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 2)(NOTE: PLEASE SHOW GROUNDING
 ELECTRODEGOING TO BUILDING STEEL AND
 COLD WATER
 PER 250-50
  
 3)NOTE: PLEASE NOTE SERVICE ENTRANCE
 CONDUCTORS SHOWN AT 3-00`S "THIN".
 SHOWN FROM METER TO PANEL? PLEASE
 CLARIFY THIS SIZE AND INSULATION TYPE.??
  
 4)NOTE: PLEASE SEE ELECTRICAL NOTES<<
 "C" CONDUIT SIZE?, "D" SUB-PANEL CALCS??
  
 5) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
 6) PLEASE NOTE MISSING OUTLET(S) REQ`D
 BY 210-52E OF THE NEC.
  
 7) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
  
 8)NOTE: PLEASE SEE RISER DIAGRAM,, PLEAS
 E CLARIFYNOTE SHOWING2-#3`S,1-#2 IN
 1/2" CONDUIT. FIRST CONDUIT IS WAY TOO
 SMALL AND WHAT DOES THIS GO TO.
  
 9)NOTE: PLEASE SHOW SERVICE ENTRANCE
 CONDUCTORS ON RISER.
  
 PLEASE CLARIFY AND SUBMIT ALL THE ABOVE
 INFORMATION FOR REVIEW. IF THERE ARE
 ANY QUESTIONS PLEASE CALL.
  