2001-07-13 00:00:00THIRD CHECKLIST:
 1-ENERGY CALCULATIONS ARE WRONG:
 A)THIS IS NOT A NEW BUILDING.
 B)NUMBER OF UNITS IS WRONG.
 C)NO INFORMATION ON FLOOR TYPES.
 D)WHAT ABOUT UNITS ON THE FIRST FLOOR?
 E)OWNER/AGENT TO SIGN AND DATE AT THE
 BOTTOM OF ENERGY CALCULATIONS FORM.
 2-CLEARLY SPECIFY SIZE & TYPE OF EGRESS
 WINDOWS. WHAT'S A 24EH WINDOW?
 -PRODUCT APPROVAL SUBMITTED IS FOR
 SINGLE HUNG WINDOWS. A 24SH WINDOW
 DOESN'T COMPLY WITH THE MINIMUM EGRESS
 REQUIREMENTS OF SEC. 1005.4 SBC 1997.
 3-SPECIFY SIZE OF ENTRY DOORS TO COMPLY
 WITH TABLE 1004 SBC 1997.
 4-PRODUCT APPROVAL FOR DOORS REQUIRES A
 2X STRUCTURAL BUCK. ENGINEER TO
 PROVIDE 2X STRUCTURAL BUCK DETAIL.
 -PROVIDE BUCK DETAIL FOR WINDOWS TOO.
 5-NEED TO APPLY FOR SEPARATE PERMITS FOR
 MECHANICAL, PLUMBING & ELECTRICAL WORK
 6-NEED TO APPLY FOR SEPARATE PERMITS FOR
 FENCE AND FOR PARKING WORK.
 7-SPECIFY HOW IS THE ONE HOUR TENANT
 SEPARATION ACHIEVED BETWEEN THE FIRST
 AND SECOND FLOOR. SEC 704.3 SBC 1997.
 8-CONTRACTOR NEEDS TO UPDATE INSURANCE.
 9-SEE COMMENTS BY THE FIRE CAPTAIN.
 10-ENGINEER TO SEE COMMENTS ON PLANS.
  
  
 NOTE:
 ENGINEER NEEDS TO REVISE ORIGINAL DWGS
 AND PROVIDE THE REQUESTED INFORMATION.