| 2001-07-13 00:00:00 | THIRD CHECKLIST: |
| | 1-ENERGY CALCULATIONS ARE WRONG: |
| | A)THIS IS NOT A NEW BUILDING. |
| | B)NUMBER OF UNITS IS WRONG. |
| | C)NO INFORMATION ON FLOOR TYPES. |
| | D)WHAT ABOUT UNITS ON THE FIRST FLOOR? |
| | E)OWNER/AGENT TO SIGN AND DATE AT THE |
| | BOTTOM OF ENERGY CALCULATIONS FORM. |
| | 2-CLEARLY SPECIFY SIZE & TYPE OF EGRESS |
| | WINDOWS. WHAT'S A 24EH WINDOW? |
| | -PRODUCT APPROVAL SUBMITTED IS FOR |
| | SINGLE HUNG WINDOWS. A 24SH WINDOW |
| | DOESN'T COMPLY WITH THE MINIMUM EGRESS |
| | REQUIREMENTS OF SEC. 1005.4 SBC 1997. |
| | 3-SPECIFY SIZE OF ENTRY DOORS TO COMPLY |
| | WITH TABLE 1004 SBC 1997. |
| | 4-PRODUCT APPROVAL FOR DOORS REQUIRES A |
| | 2X STRUCTURAL BUCK. ENGINEER TO |
| | PROVIDE 2X STRUCTURAL BUCK DETAIL. |
| | -PROVIDE BUCK DETAIL FOR WINDOWS TOO. |
| | 5-NEED TO APPLY FOR SEPARATE PERMITS FOR |
| | MECHANICAL, PLUMBING & ELECTRICAL WORK |
| | 6-NEED TO APPLY FOR SEPARATE PERMITS FOR |
| | FENCE AND FOR PARKING WORK. |
| | 7-SPECIFY HOW IS THE ONE HOUR TENANT |
| | SEPARATION ACHIEVED BETWEEN THE FIRST |
| | AND SECOND FLOOR. SEC 704.3 SBC 1997. |
| | 8-CONTRACTOR NEEDS TO UPDATE INSURANCE. |
| | 9-SEE COMMENTS BY THE FIRE CAPTAIN. |
| | 10-ENGINEER TO SEE COMMENTS ON PLANS. |
| | |
| | |
| | NOTE: |
| | ENGINEER NEEDS TO REVISE ORIGINAL DWGS |
| | AND PROVIDE THE REQUESTED INFORMATION. |