| 2001-05-01 00:00:00 | 1) ALL UNDERGROUND FIRE MAINS ARE TO BE | | | LISTED FOR FIRE PROTECTION SERVICE AND | | | COMPLY WITH NFPA 24, FIRE SERVICE MAINS | | | AND THEIR APPURTENANCES. | | | 2) PROVIDE SEPARATE PLANS AND PERMITS | | | FOR THE INSTALLATION OF THE FIRE | | | SPRINKLER SYSTEM AND FIRE PUMP ASSEMBLY. | | | 3) PROVIDE SEPARATE PLANS AND PERMITS | | | FOR THE INSTALLATION OF THE FIRE ALARM | | | SYSTEM. CUT SHEETS, WIRING DIAGRAM, AND | | | BATTERY CALCULATIONS ARE TO BE PROVIDED. | | | 4) FIRE SPRINKLER SYSTEM AND FIRE ALARM | | | SYSTEMS ARE TO BE SUPERVISED BY A | | | LICENSED UL LISTED CENTRAL STATION | | | APPROVED BY THE FIRE RESCUE DEPARTMENT. | | | 5) EMERGENCY LIGHTING REQUIRED IN | | | CARD,PARTY, TV ROOM. | | | 6) INGRESS AND EGRESS INTO THE COMPLEX | | | SHALL BE A MINIMUM OF TWENTY FEET IN | | | CLEAR WIDTH. BATTERY BACK-UP FEATURE | | | SHALL BE PROVIDED FOR GATE-ARMS SHOULD | | | LOSS OF POWER OCCUR. TRAFFIC CALMING | | | HUMPS ARE NOT TO INTERFERE WITH FIRE | | | RESCUE MOVEMENT INTO THE COMPLEX. | | | 7) PLEASE INDICATE PORTABLE FIRE | | | EXTINGUISHER LOCATIONS. | | | 8) PLEASE EXPLAIN RATIONALE FOR THE | | | SINGLE FIRE DEPARTMENT CONNECTION SHOWN | | | ON THE OTHER DRAWINGS. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|