| Date |
Text |
| 2001-03-14 00:00:00 | 1) PLEASE INDICATE FIRE RESCUE ACCESS |
| | INTO THE APARTMENT COMPLEX. THE OPENING |
| | THAT FIRE RESCUE IS EXPECTED TO PASS |
| | THRU MUST BE AT LEAST 20 FEET IN CLEAR |
| | WIDTH. HOW DOES FIRE RESCUE EQUIPMENT |
| | PASS THE SECURITY FEATURES PLANNED FOR |
| | THE COMPLEX DRIVE OPENINGS. |
| | 2) UNDERGROUND FIRE LINES, FIRE HYDRANTS |
| | AND APPURTENACES TO COMPLY WITH NFPA 24. |
| | THIS EQUIPMENT TO MEET UTILITY AND FIRE |
| | RESCUE STANDARDS. WET FIRE HYDRANTS ARE |
| | TO BE PROVIDED PRIOR TO, DURING AND |
| | AFTER CONSTRUCTION. |
| | 3) PLEASE INDICATE IF GATES OR FRAME |
| | ARMS WILL BE PROVIDED FOR SECURITY |
| | PURPOSES. |
| | 4) BUILDING ADDRESSES REQUIRED PER CITY |
| | CODE REQUIREMENTS. |
| | 5) CLUBHOUSE TO PROVIDE PROVISIONS FOR |
| | AT LEAST TWO HANDICAPPED PERSONS. |
| | 6) PLEASE INDICATE HOW THE DRYER CHASE |
| | CAN BE CLEANED OF COMBUSTIBLE LINT |
| | BUILD-UP. PLEASE PROVIDE UL NUMBERS FOR |
| | ALL SHAFTS. |
| | 7) NO HYDRAULIC CALCULATIONS PROVIDED |
| | WITH FIRE SPRINKLER DRAWINGS. ALL |
| | BUILDINGS ARE TO BE COMPLETELY FIRE |
| | SPRINKLER PROTECTED. ALL ELECTRICAL, |
| | MECHANICAL AND SERVICE ROOMS ARE TO BE |
| | PROTECTED WITH FIRE SPRINKLER HEADS. |
| | ALSO ALL VERTICAL SHAFTS ARE TO BE |
| | FIRE SPRINKLER PROTECTED. |
| | 8) EMERGENCY LIGHTING REQUIRED IN FIRE |
| | PUMP ROOM. OKAY, LOCATED ON PLANS. |
| | 9) ALL BUILDINGS THREE STORIES OR MORE |
| | AND 50 FEET IN HEIGHT MUST HAVE |
| | STANDPIPE SYSTEMS IN ACCORDANCE WITH |
| | NFPA 14. |
| | 10) HANDRAILS AND GUARDS TO COMPLY WITH |
| | NFPA 101, THE LIFE SAFETY CODE, 1985 |
| | EDITION. |
| | 11) MORE DETAILS NEEDED FOR FIRE PUMP |
| | EQUIPMENT AND APPURTENANCES. |
| | 12) IS ACCESS PROVIDED INTO THE WOOD |
| | TRUSS AREA. |
| | 13) TENANT SEPARATIONS TO COMPLY WITH |
| | BUILDING CODE REQUIREMENTS. |
| | 14) PLEASE BE ADVISED OF THE STRETCHER |
| | REQUIREMENTS OF THE STANDARD BUILDING |
| | CODE, SECTION 3003.4 FOR BUILDINGS FOUR |
| | OR MORE FLOORS. |
| | 15) PLEASE PROVIDE INTERIOR FINISH |
| | CLASSIFICATION INFORMATION. |
| | 16) IS BATTERY BACK-UP PLANNED FOR THE |
| | SECURITY FEATURES AT THE ENTRANCE SHOULD |
| | LOSS OF POWER RESULT. |
| | 17) DOES THE NOTE ON PAGE E12 MEAN |
| | ONLY A SINGLE FIRE ALARM PANEL FOR THE |
| | COMPLEX. WHAT HAPPENS WHEN THIS PANEL |
| | IS DOWN FOR REPAIRS OR REPLACEMENT. |
| | |
| | CAPTAIN MIKE CARSILLO |
| | 659-8096,EXT.8497 |
| | 835-2910 |