Plan Review Notes
Plan Review Notes For Permit 01030517
Permit Number 01030517
Review Stop B
Sequence Number 1
Notes
Date Text
2001-04-11 00:00:00PROJECT: PENNACLE PALMS
 601 EXECUTIVE CENTER DR
 CLUBHOUSE: 01030517
 BUILD. "A" 01040479
 BUILD. "B" 01040480
 BUILD. "C" 01040481
 BUILD. "D" 01040482
 ARCHITECT REG
 P 659-2383
 F
 CONTACT PERSON:SEAN (305)561-3901
 F(305)859-9858
 DELAN CONST: (PROJECT)
  
 THE COMMENTS FOUND IN THIS REVIEW WILL
 BE COMMON TO BUILDINGS A,B,C & D. BUILD-
 ING "C" COMMENTS WILLBE MORE RESTRICTIVE
 SINCE ITS A TYPE II BUILDING.
  
 1)- DOCUMENTS SHOWING OWNERSHIP, THE
 PROPERTY APPRAISERS OFFICE INDICATES
 THAT ASPENWOODS IS STILL THE OWNER.
  
 2)- BEFORE ISSUANCE OF A PERMIT A NOTICE
 OF COMMENCEMENT HAS TO BE FILED & RECORD
 ED WITH THE COUNTY,ONCE FILED WORK HAS
 TO START WITHIN 90 DAYS OR IT WILL BE
 VOID AND WILL BE REQUIRED TO BE REFILED.
  
 3)- THE ADDRESS THAT WAS GIVEN IS WRONG.
 THE CORRECT ADDRESS WILLBE 601 EXECUTIVE
 CENTER DRIVE. ONE SITE ADDRESS WILL BE
 GIVEN AND EACH BUILDING WILL BE ASSIGNED
 A TENANT(BUILDING) ADDRESS.
  
 4)- THE PLANS INDICATE THAT ARDAMAN &
 ASSOCIATES, INC. HAS COMPLETED A SOILS
 TEST, THE BUILDING DEPARTMENT WILL NEED
 A COPY INDICATING THE MINIMUM SAFE BEAR-
 ING CAPACITY OF THE SOIL.
  
 5)MISSING IS THE DESIGN CRITERIA FOR THE
 BUILDINGS. BUILDINGS < 60' IN HEIGHT CAN
 BE DESIGNED TO CHAPTER 16 OF THE SBC.
 BUILDINGS > 60' ARE TO BE DESIGNED TO
 ASCE 7-95.
  
 6)- COMPONENTS & CLADDING:SBC 1606.2.6.2
 ARE TO BE DESIGNED TO MEET WIND LOADS,
 A)- WINDOW & DOOR BUCKS: THE DESIGNER
 OF RECORD NEEDS TO INDICATE THE
 FASTENING SCHEDULE AND THE TYPE OF
 FASTTENERS TO BE USED.
 B)- DOORS, SWING OR OVERHEAD NEED TO
 HAVE PROOF OF PRODUCT TESTING FOR
 WIND. IF THERE IS GLAZING IN THE
 ASSEMBLY SEE WPB POLICY FOR GLAZED
 OPENINGS. WE ACCEPT SBCCI REPORTS
 AS WELL AS DADE COUNTY ACCEPTANCE
 REPORTS.
 C)- GLAZED OPENINGS,WINDOWS DOORS,SLID-
 ING GLASS DOORS WILL REQUIRE PRO-
 DUCT TESTING FOR LARGE MISSLE IM-
 PACT TESTING FOR GLAZED OPENINGS,
 SEE ATTACHED COPY OF THE CITY
 POLICY FOR DETAILS, LARGE, MID OR
 HIGH-RISE STRUCTURES.SBC 1606.4 &
 1707.4.1 AMENDMENTS.
 D)- ROOFING MATERIALS: SBC 1503.3.2.
 ARE TO BE DESIGNED TO 110 MPH WIND.
 1707.5 CEMENT TILE ARE TO BE TESTED
 FOR THERE MOMENT OF OVER TURNING,
 PRODUCT APPROVAL TESTING REPORTS
 ARE REQUIRED.
 E)- SATELLITE DISHES: SEE ATTACHED CITY
 POLICY, REQUIREMENTS FOR PERMITTING
 (COMMERCIAL).
  
 7)- SBC 803.3 PLEASE INDICATE THE MINI-
 MUM INTERIOR FINISH CLASSIFICATION FOR
 THE INTERIOR OF STRUCTURES.
  
 8)- SBC 2304.1.2 COUNTY AMENDMENTS:SOIL
 TREATMENT FOR TERMITES REQUIRED BEFORE
 THE PLACEMENT OF CONCRETE.
  
 9)- SHEET A 2.1 SEC 2/A 5.3 IS MISSING
 THE VERTICAL SHAFT INFORMATION, 4 STOR-
 IES OR MORE REQUIRES 2 HR TABLE 705.2,
 LESS THAN 4 STORIES 1 1/2 HR.
  
 10)- A 9.0 DOOR SCHEDULE DOESN'T INDI-
 CATE THE TYPE OF LABEL NOR THE RATING
 REQUIRED FOR THE DOOR, SBC 104.2.2 ADD-
 ITIONAL INFO REQUIRED.
  
 11)- FL. STATE STATUTE 553.895 WILL
 REQUIRE FIRE SPRINKLER PLANS SINCE THE
 BUILDING WILL BE USED AS A PUBLIC
 LODGING ESTABLISHMENT.SBC 903.7.6.
  
 12)- SBC 905.2 AUTOMATIC FIRE DETECTION
 SYSTEMS REQUIRED.
  
 13)- REFUSE ROOM, PLEASE PROVIDE ADD.
 INFORMATION ON THE FEFUSE CHUTE, 4 STOR-
 IES OR MORE REQUIRES 2 HR RATING, 1 1/2
 HR. PROTECTIVES, , < 4 STORIES 1 1/2
 RATING.
  
 14)- ADDITONAL INFORMATION: A 8.0 STAIR
 SECTION (5) FIRST FLOOR THE SPACE UNDER
 THE STAIRWELL IN DICATES A 3'-0" OPENING
 IS THIS GOING TO BE USED FOR STORAGE?
  
 15)- SHEET A 3.1 DETAIL 2 INDICATES
 METAL LATH, SBC 2504.2.2/ ASTM C 1063
 WHICH WILL BE USED FLAT RIBBED EXSPANDED
 METAL OR 3/8" RIBBED LATH? NAIL SPACING
 FOR HORIZONTAL SURFACES, & PENETRATION
 REQUIRED FOR NAILS OR STAPLES?
  
 16)- S-8 DEPICTS A WX8.5 STEEL BEAM,
 FOR THE A/C ROOF UNITS TO ATTACH TO.
 SHOW ATTACHMENT DETAILS FOR STEEL TO
 BUILDING AND THE WEILD REQUIRED FOR THE
 STRUCTURAL COMPONENTS, 18" MIN. CLEAR-
 ENCE REQUIRED.
  
 17)- TYPE II & TYPE IV BUILDINGS TABLE
 600, 602: TYPE II, 606 : TYPE IV BUILD-
 INGS REQUIRE NONCOMBUSTIBLE MATERIALS
 FOR TRUSSES AND SHEATHING.
  
 18)- TABLE 600:TYPE II BUILDINGS SHOW
 FIRE RESISTANCE RATINGS FOR FLOORS,
 COLUMNS,& BEAMS.
  
 19)- SBC 609.2 NON COMBUSTIBLE MATERIALS
 ARE TO BE USED IN INTERIOR WALLS TYPEII
 NOR TYPE IV CONSTRUCTION. SBC 707
 COMBUSTIBLES IN CONSEALED SPACES.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 E 8412