| Notes |
| Date |
Text |
| 2001-04-25 00:00:00 | ****************** UNSAT ************* | | | | | | 1)NOTE: PLEASE NOTE THAT NOT ALL NOTES | | | WERE ADDRESSED. | | | | | | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | THE CODE ARTYS: WERE WRITTEN ON PLANS?? | | | THIS DOES NOT GIVE US THE AIC RATING | | | FORNEW EQUIPMENT. | | | | | | 3)NOTE: PLEASE NOTE THAT ALL THE OTHER | | | CHANGES THAT WERE MADE, WERE DONE IN | | | PENCIL? THIS IS NOT PERMITTED UNDER | | | 104.2 AND 104.2.7. ALSO ALL PLANS THAT | | | ARE SIGNED AND SEALED BY AN | | | ARCH/ENGINEER ARE TO BE DONE BY THAT | | | PERSON PER F.S. AND F.A.C 471.025 AND | | | 481.221. | | | | | | PLEASE HAVE PLANS RE-DONE UNDER COUNTY | | | AND CITYWIDE ADMINISTRATIVE CODE. | | | 104.2& .7. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|