Plan Review Notes
Plan Review Notes For Permit 01030464
Permit Number 01030464
Review Stop E
Sequence Number 2
Notes
Date Text
2001-04-25 00:00:00****************** UNSAT *************
  
 1)NOTE: PLEASE NOTE THAT NOT ALL NOTES
 WERE ADDRESSED.
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 THE CODE ARTYS: WERE WRITTEN ON PLANS??
 THIS DOES NOT GIVE US THE AIC RATING
 FORNEW EQUIPMENT.
  
 3)NOTE: PLEASE NOTE THAT ALL THE OTHER
 CHANGES THAT WERE MADE, WERE DONE IN
 PENCIL? THIS IS NOT PERMITTED UNDER
 104.2 AND 104.2.7. ALSO ALL PLANS THAT
 ARE SIGNED AND SEALED BY AN
 ARCH/ENGINEER ARE TO BE DONE BY THAT
 PERSON PER F.S. AND F.A.C 471.025 AND
 481.221.
  
 PLEASE HAVE PLANS RE-DONE UNDER COUNTY
 AND CITYWIDE ADMINISTRATIVE CODE.
 104.2& .7.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372