2001-03-26 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT LOAD
 CALCULATIONS AND LOADS ON PANEL
 SCHEDULE ARE NOT COMPLETE. PLEASE DO
 SO. 215-5.
  
 2)NOTE: PLEASE NOTE LOADS FOR LIGHTING,
 WELL PUMP, SPRINKLER PUMP??
  
 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 4) NOTE: PLEASE SHOW GROUNDING
 ELECTRODE GOING TO BUILDING STEEL AND
 COLD WATER. PER 250-50
 PLEASE NOTE THAT WE ARE
 UNDER THE "99" NEC. THERE IS A NOTE REF
 TO
 ART 250-83C? THIS IS NOT IN THE "99"NEC.
  
 5) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 PLEASE NOTE THAT IF THERE IS GOING TO BE
 CATV AND OR TELEPHONE IN THE HOUSE THEN
 LOCATIONS NEED TO BE SHOWN ON PLANS.
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372