| Plan Review Notes For Permit 01030451 |
| Permit Number |
01030451 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-03-13 00:00:00 | 1) DUCT SMOKE DETECTORS ARE REQUIRED IN | | | AIR HANDLING SYSTEMS OVER 2000 CFM. WHEN | | | ACTIVATED, THESE DEVICES ARE TO SHUT | | | DOWN AIR HANDLING SYSTEMS AND ACTIVATE | | | THE FIRE ALARM SYSTEM. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|