| Plan Review Notes For Permit 01030429 |
| Permit Number |
01030429 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-03-29 00:00:00 | PROVISO: 03/29/01 | | | 1)- SBC 1707.4 EXTERIOR DOOR & WINDOW | | | ASSEMBLIES: ALL GLAZED OPENINGS REQUIRE | | | TESTING FOR A PERIOD OF TIME OF 10 | | | SECOND PERIOD AT A LOAD EQUAL TO 1.5 | | | TIMES THE DESIGN PRESSURE. MISSING | | | REPORTS: | | | A)- FIXED WINDOWS | | | B)- MULLIONS | | | C)- SLIDING WINDOWS | | | D)- FRENCH DOORS | | | 2)- SBC 1707.4.1- STORM SHUTTERS REQUIRE | | | A KEY PLAN WITH A FASTENING SCHEDULE. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659 -8096 EX 8412 |
|