Plan Review Notes For Permit 01030426
Permit Number 01030426
Review Stop E
Sequence Number 2
Notes
Date Text
2001-04-17 00:00:00****************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT THE LOAD
 CALCULATIONS THAT WERE SUBMITTED SHOW
 LOAD FOR NEW GARAGE ONLY? WHAT ABOUT
 LOAD IN EXSITING HOUSE? WHAT SIZE IS
 EXISTING SERVICE THAT FEEDS NEW
 EQUIPMENT?
  
 2)NOTE: PLEASE NOTE STILL NOTHING
 SUBMITTED SHOWING CONDUIT SIZES ON
 RISER OR
 WIRE SIZES ON RISER OR WIRE SIZES GOING
 TO MAIN HOUSE? PLEASE SHOW.
  
 3)NOTE: PLEASE NOTE PLANS SHOW OPTIONAL
 FEED TO HOUSE BEING OVERHEAD? AT 10`FT.
 PLEASE SEE 230-24 FOR CLEARENCES.
  
  
 4)NOTE: PLEASE NOTE THAT NOW PLANS SHOW
 NEW EQUIPMENT BEING INSTALLED.
 PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 5)NOTE: PLEASE CLARIFY SMALL APPLIANCE
 CIRCUITS SHOWN FOR GARAGE?
  
 6) NOTE: PLEASE SHOW GROUNDING ELECTRODE
 GOING TO BUILDING STEEL AND COLD WATER
 PER 250-50. GROUNDING FOR DETACHED BLDG.
  
 7)NOTE PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372