| Notes |
| Date |
Text |
| 2001-03-29 00:00:00 | *************** UNSAT ****************** | | | | | | 1)NOTE: PLEASE NOTE THAT THERE IS NOT | | | ENOUGH ELECTRICAL DETAIL FOR REVIEW OF | | | FEED/OR SERVICE TO GARAGE. WIRE SIZES, | | | CONDUITS, ETC. WHERE IS POWER COMING | | | FROM.? | | | 2)NOTE: PLEASE SEE 210-8 FOR ALL | | | OUTLETSIN GARAGE TO BE GFI /GFI | | | PROTECTED. | | | | | | PLEASE SUBMIT MORE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|