| Plan Review Notes For Permit 01030349 |
| Permit Number |
01030349 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-04-11 00:00:00 | ******************PROVISO*************** | | | | | | PLAN M0.1 NOTE #14, SHOULD NOT HAVE BEEN | | | REMOVED, FAN SHUTDOWN BY DUCT SMOKE DETE | | | CTOR FOR UNITS SERVING A COMMON PLENUM I | | | S REQUIRED WITH NOTIFICATION TO ALARM/ST | | | ROBE IN NORMALLY OCCUPIED AREAS. | | | | | | M2.1 FIRE DAMPER IS NOW GOING TO BE | | | UNDER THE SCOPE OF THE ADJACENT TENENT | | | BUILD OUT, PLANS APPROVED 1/16/01 | | | INDICATE THE FIRE DAMPER WAS EXISTING. | | | THIS FIRE DAMPER MUST REMAIN OR BE REPLA | | | CED WITH THIS BUILD OUT. |
|