2001-04-11 00:00:00******************PROVISO***************
  
 PLAN M0.1 NOTE #14, SHOULD NOT HAVE BEEN
 REMOVED, FAN SHUTDOWN BY DUCT SMOKE DETE
 CTOR FOR UNITS SERVING A COMMON PLENUM I
 S REQUIRED WITH NOTIFICATION TO ALARM/ST
 ROBE IN NORMALLY OCCUPIED AREAS.
  
 M2.1 FIRE DAMPER IS NOW GOING TO BE
 UNDER THE SCOPE OF THE ADJACENT TENENT
 BUILD OUT, PLANS APPROVED 1/16/01
 INDICATE THE FIRE DAMPER WAS EXISTING.
 THIS FIRE DAMPER MUST REMAIN OR BE REPLA
 CED WITH THIS BUILD OUT.