| Plan Review Notes For Permit 01030278 |
| Permit Number |
01030278 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-03-11 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 2)NOTE: NO WIRE SIZES ON RISER DIAGRAM? | | | CONDUIT SIZE? GROUND SIZE? COLD WATER? | | | | | | | | | 3)NOTE: SHOW ALL MEANS OF EGRESS LIGHTIN | | | G AND ALL SWITH LEGS FOR CONTROLL. | | | 210-70. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|