| Plan Review Notes For Permit 01030274 |
| Permit Number |
01030274 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-03-11 00:00:00 | ***************** UNSAT *************** | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 2) NOTE: PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S) PER 210-11-C-3. | | | MUST BE 20A AND #12AWG. | | | | | | 3) PLEASE CLARIFY EQUIPMENT GROUNDING | | | METHOD BETWEEN FIRST MEANS OF DISCONNECT | | | AND PANEL(S). EQUIPMENT GROUNDING | | | CONDUCTORS ARE TO BE SIZED BY 250-122. | | | | | | | | | 4) PLEASE NOTE MISSING OUTLET(S) REQ`D | | | BY 210-52E OF THE NEC. | | | | | | | | | 5) PLEASE NOTE EITHER MISSING EGRESS | | | LIGHTING AND/OR CLARIFY EGRESS LIGHTING | | | PER 210-70 OF THE NEC. FIXTURE REQ`D AT | | | J-BOX SHOWN IN HALLWAY TO MASTER BATH. | | | | | | 6)NOTE: PLEASE NOTE MISSING OUTLET FOR | | | HALLWAY PER 210-52H | | | | | | 7) NOTE: PLEASE SHOW ALL OUTLET SPACING | | | TO MEET 2`,6`,12` RULE PER 210-52. | | | UPSTAIRS | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|