2001-03-29 00:00:00BUILDING PLAN REVIEW
 01030274
 7640 MONTE VERDE LA
 CLASSIC/ ZUCKERMAN
 (954) 345-2727
  
 1)- SBC 104.2.2: DISCREPANCY, SHEET A-1
 VS. A-3. COVERED PATIO A-3 SHOWS A 2ND
 COLUMN.
  
 2)- SBC 1606.2.6.2 COMPONENTS & CLADDING
 PRODUCT APPROVAL REPORTS FOR THE FOLLOW-
 ING ARE MISSING:
 A) SINGLE HUNG WINDOWS; SBCCI OR
 DADE COUNTY PRODUCT APPROVALS.
 B) SWING DOORS (GLAZED OPENINGS)
 DADE COUNTY OR SBCCI REPORT
  
 3)- WINDOW "K" A TESTING REPORT SHOWING
 THE MUTTINS? NOT A MULLION REPORT, THEY
 ARE NEEDED TO SHOW 2 WINDOWS BEING
 JOINED TOGETHER.
  
 4)- SBC 2305.2.2 DRAFT STOPPING IN
 FLOOR / CEILING ASSEMBLIES, NOT EXCEED-
 ING 500 SQ. FT. IN ANY AREA.
  
 5)- SBC 2309.6 ATTIC ACCESS FOR THE
 2ND FLOOR.
  
 6)- PLANS TO COUNTY FOR THE IMPACT FEES.
  
 7)- STATE RADON FEES OF $40.24 PAID TO
 THE CITY.