| 2001-03-06 00:00:00 | *************** UNSAT **************** |
| | |
| | 1)NOTE: PLEASE NOTE, SPACE MUST HAVE |
| | A 2 (TWO) HOUR FIRE WALL ALL THE TO |
| | ROOFLINE IF SPACE IS GOING TO BE A |
| | SEPARATE SERVICE. 230-2. IF THE SERVICE |
| | SHOWN IS THE SAME SERVICE FEEDING THE |
| | SAME BLDG THEN THIS WOULD BE OK? PLEASE |
| | CLARIFY. |
| | |
| | 2)NOTE: PLEASE NOTE, THAT PER F.A.C. |
| | 553-79 6A 277/480V SERVICES MUST BE |
| | SIGNED AND SEALED BY AN P.E. |
| | |
| | 3)NOTE: PLEASE NOTE THAT ALL CONTINUOUS |
| | LOADS ARE TO FIG AND SHOWN AT 125% |
| | PER 215-2,3 |
| | |
| | 4)NOTE: PLEASE PROVIDE CLARIFICATION ON |
| | THE INSTALLATION OF TRANSFORMER PER |
| | 450-13B. |
| | |
| | 5) PLEASE CLARIFY EQUIPMENT GROUNDING |
| | METHOD BETWEEN FIRST MEANS OF |
| | DISCONNECTAND PANEL(S). EQUIPMENT |
| | GROUNDING |
| | CONDUCTORS ARE TO BE SIZED BY 250-122. |
| | ETC. ALL LOCATION |
| | |
| | 6)NOTE: PLEASE CLARIFY GROUND FOR |
| | TRANSFORMER. |
| | |
| | 7)NOTE: PLEASE CLARIFY LOAD SHOWN FOR |
| | PANEL "H" LOADS SHOWN ARE 1500W AND |
| | 15000W FOR TRANSFORMER, THEN JUMPS TO |
| | 90,000W IN LOAD CALC.??? |
| | |
| | |
| | 8)NOTE: MEANS OF DISCONNECT CANNOT BE |
| | IN ANOTHER PERSONS TENANT SPACE! PLEASE |
| | CLARIFY THIS AS EXISTING BLGS ELEC ROOM. |
| | |
| | |
| | |
| | PLEASE SUBMIT ALL THE ABOVE INFOAMTION |
| | FOR REVIEW. IF THERE ARE ANY QUESTIONS |
| | PLEASE CALL. |
| | |