Plan Review Notes
Plan Review Notes For Permit 01030199
Permit Number 01030199
Review Stop R
Sequence Number 5
Notes
Date Text
2002-02-08 00:00:00TRUSS DRAWINGS SECOND REVIEWFROM
 PREVIOUS CHECKLIST DATED 01-02-02:
 1-ENGINEER OF RECORD TO REVIEW ALL TRUSS
 DRAWINGS PRIOR TO SUBMITTAL. ENGINEER
 OF RECORD IS DON ARPIN NOT ALBERT A.
 GARGIULO. IF CHANGING ENGINEER, THEN
 FOLLOW CHAPTER 61G15-27 FROM FLORIDA
 BOARD OF PROFESSIONAL ENGINEERS
 (PROCEDURE FOR ADOPTION OF ANOTHER'S
 WORK).
 2-TRUSS LAYOUT DOESN'T MATCH FRAMING
 PLAN SUBMITTED BY ENGINEER OF RECORD.
 APPROVED PLANS SHOW EXISTING ROOF AT
 MAIN HOUSE, WHILE TRUSS LAYOUT CALLS
 FOR NEW ROOF FRAMING.
 -ALSO, FRAMING AT GARAGE AREA DOESN'T
 MATCH EITHER.
 -REVISE ROOF FRAMING PLANS AS REQUIRED
 TO MATCH AND PROVIDE CORRESPONDING
 TRUSS ANCHOR SCHEDULE AND SPECS AS
 REQUIRED.
 3-PROVIDE ITEMS REQUESTED ON PROVISO
 DATED 7-20-01.
 4-PROVIDE PRODUCT APPROVALS FOR OVERHEAD
 GARAGE DOORS.
 5-COMMENTS ON PRODUCT APPROVAL SUBMITTED
 A)SITE SPECIFIC FORM IS NOT LEGIBLE.
 B)SITE SPECIFIC FORM TO BE SIGNED,SEALED
 AND DATED BY THE MANUFACTURER'S ENG'R
 AND BY THE ENGINEER OF RECORD AS WELL.
 C)MANUFACTURER'S ENGINEER TO PROVIDE
 ORIGINAL SIGNATURE, DATE AND SEAL ON
 ALL DOCUMENTS SUBMITTED FOR PUBLIC
 RECORDS. CHAPTER 471 FLORIDA STATUTES.
 D)WHO'S ARCHITRAVE-DALE POSEY-ARCHITECT?
 HE HAS NOTHING TO DO IN THIS PROJECT,
 BUT HE IS BEING ADDRESSED TO IN ALL
 ENGINEERED TRUSSES. REVISE AS REQ'D.
  
 NOTE: RESUBMITTAL FEES WILL BE CHARGED.