| Date |
Text |
| 2002-02-08 00:00:00 | TRUSS DRAWINGS SECOND REVIEWFROM |
| | PREVIOUS CHECKLIST DATED 01-02-02: |
| | 1-ENGINEER OF RECORD TO REVIEW ALL TRUSS |
| | DRAWINGS PRIOR TO SUBMITTAL. ENGINEER |
| | OF RECORD IS DON ARPIN NOT ALBERT A. |
| | GARGIULO. IF CHANGING ENGINEER, THEN |
| | FOLLOW CHAPTER 61G15-27 FROM FLORIDA |
| | BOARD OF PROFESSIONAL ENGINEERS |
| | (PROCEDURE FOR ADOPTION OF ANOTHER'S |
| | WORK). |
| | 2-TRUSS LAYOUT DOESN'T MATCH FRAMING |
| | PLAN SUBMITTED BY ENGINEER OF RECORD. |
| | APPROVED PLANS SHOW EXISTING ROOF AT |
| | MAIN HOUSE, WHILE TRUSS LAYOUT CALLS |
| | FOR NEW ROOF FRAMING. |
| | -ALSO, FRAMING AT GARAGE AREA DOESN'T |
| | MATCH EITHER. |
| | -REVISE ROOF FRAMING PLANS AS REQUIRED |
| | TO MATCH AND PROVIDE CORRESPONDING |
| | TRUSS ANCHOR SCHEDULE AND SPECS AS |
| | REQUIRED. |
| | 3-PROVIDE ITEMS REQUESTED ON PROVISO |
| | DATED 7-20-01. |
| | 4-PROVIDE PRODUCT APPROVALS FOR OVERHEAD |
| | GARAGE DOORS. |
| | 5-COMMENTS ON PRODUCT APPROVAL SUBMITTED |
| | A)SITE SPECIFIC FORM IS NOT LEGIBLE. |
| | B)SITE SPECIFIC FORM TO BE SIGNED,SEALED |
| | AND DATED BY THE MANUFACTURER'S ENG'R |
| | AND BY THE ENGINEER OF RECORD AS WELL. |
| | C)MANUFACTURER'S ENGINEER TO PROVIDE |
| | ORIGINAL SIGNATURE, DATE AND SEAL ON |
| | ALL DOCUMENTS SUBMITTED FOR PUBLIC |
| | RECORDS. CHAPTER 471 FLORIDA STATUTES. |
| | D)WHO'S ARCHITRAVE-DALE POSEY-ARCHITECT? |
| | HE HAS NOTHING TO DO IN THIS PROJECT, |
| | BUT HE IS BEING ADDRESSED TO IN ALL |
| | ENGINEERED TRUSSES. REVISE AS REQ'D. |
| | |
| | NOTE: RESUBMITTAL FEES WILL BE CHARGED. |