| 2002-01-02 00:00:00 | TRUSS DRAWINGS CHECKLIST: |
| | 1-ENGINEER OF RECORD TO REVIEW ALL TRUSS |
| | DRAWINGS PRIOR TO SUBMITTAL. |
| | 2-CLARIFY WHY IS THERE ANOTHER ENGINEER |
| | CERTIFYING FOR THE STRUCTURAL |
| | CONNECTIONS. THE ENGINEER OF RECORD IS |
| | DON ARPIN, NOT ALBERT GARGIULO. SEE |
| | CHAPTER 471 FLORIDA STATUTES. |
| | 3-TRUSS LAYOUT DOESN'T MATCH FRAMING |
| | PLANS SUBMITTED BY ENGINEER OF RECORD. |
| | APPROVED PLANS SHOW EXISTING ROOF AT |
| | MAIN HOUSE, WHILE TRUSS LAYOUT CALL |
| | FOR NEW ROOF FRAMING. ALSO, FRAMING |
| | PLAN AT GARAGE AREA DOESN'T MATCH. |
| | REVISE EITHER TRUSS DRAWINGS OR ENG'R |
| | PLANS AS REQUIRED AND PROVIDE COMPLETE |
| | ANCHOR SPECIFICATIONS AS REQUIRED. |
| | SEC. 104.2.2 CITY AMENDMENTS TO SBC/97 |
| | 4-ALL ENGINEERED TRUSSES NEED ORIGINAL |
| | SIGNATURE AND DATE AS REQUIRED BY |
| | CHAPTER 471 FLORIDA STATUTES. |
| | 5-UPDATE ALL GENERAL TRUSS DETAILS. USE |
| | ASCE 7-95 FOR 140MPH, NOT ASCE 7-93. |
| | 6-THERE IS ONLY ONE MEAN ROOF HEIGHT FOR |
| | ENTIRE BUILDING (+/- 19'-6"). |
| | SEE TABLE 1606.2A SBC 1997. TRUSSES |
| | ARE DESIGN USING DIFFERENT MEAN ROOFS. |
| | 7-INDEX OF ENGINEERED TRUSSES DOESN'T |
| | MATCH TRUSS LAYOUT. |
| | 8-ITEMS REQUESTED ON PROVISO DATED |
| | 7-20-01 ARE NOT SUBMITTED YET. PROVIDE |
| | SUCH INFORMATION BEFORE INSTALLATION |
| | TO AVOID DELAYS OR CONFLICTS. |