2002-01-02 00:00:00TRUSS DRAWINGS CHECKLIST:
 1-ENGINEER OF RECORD TO REVIEW ALL TRUSS
 DRAWINGS PRIOR TO SUBMITTAL.
 2-CLARIFY WHY IS THERE ANOTHER ENGINEER
 CERTIFYING FOR THE STRUCTURAL
 CONNECTIONS. THE ENGINEER OF RECORD IS
 DON ARPIN, NOT ALBERT GARGIULO. SEE
 CHAPTER 471 FLORIDA STATUTES.
 3-TRUSS LAYOUT DOESN'T MATCH FRAMING
 PLANS SUBMITTED BY ENGINEER OF RECORD.
 APPROVED PLANS SHOW EXISTING ROOF AT
 MAIN HOUSE, WHILE TRUSS LAYOUT CALL
 FOR NEW ROOF FRAMING. ALSO, FRAMING
 PLAN AT GARAGE AREA DOESN'T MATCH.
 REVISE EITHER TRUSS DRAWINGS OR ENG'R
 PLANS AS REQUIRED AND PROVIDE COMPLETE
 ANCHOR SPECIFICATIONS AS REQUIRED.
 SEC. 104.2.2 CITY AMENDMENTS TO SBC/97
 4-ALL ENGINEERED TRUSSES NEED ORIGINAL
 SIGNATURE AND DATE AS REQUIRED BY
 CHAPTER 471 FLORIDA STATUTES.
 5-UPDATE ALL GENERAL TRUSS DETAILS. USE
 ASCE 7-95 FOR 140MPH, NOT ASCE 7-93.
 6-THERE IS ONLY ONE MEAN ROOF HEIGHT FOR
 ENTIRE BUILDING (+/- 19'-6").
 SEE TABLE 1606.2A SBC 1997. TRUSSES
 ARE DESIGN USING DIFFERENT MEAN ROOFS.
 7-INDEX OF ENGINEERED TRUSSES DOESN'T
 MATCH TRUSS LAYOUT.
 8-ITEMS REQUESTED ON PROVISO DATED
 7-20-01 ARE NOT SUBMITTED YET. PROVIDE
 SUCH INFORMATION BEFORE INSTALLATION
 TO AVOID DELAYS OR CONFLICTS.