2001-07-07 00:00:00CHECKLIST:
 1-SURVEY AND ELEVATION CERTIFICATE DON'T
 MATCH. FINISH FLOOR ELEVATIONS DON'T
 MATCH. PROVIDE CURRENT SURVEY WITH
 CORRECT INFORMATION.
 -PROVIDE SURVEY SHOWING PROPOSED LAYOUT
 2-DESIGN CERTIFICATION FOR BUILDING CODE
 COMPLIANCE FORM IS INCORRECT. THE MEAN
 ROOF HEIGHT AND VELOCITY PRESSURE
 DON'T MATCH. SEE TABLE 1606.2A SBC/97.
 -THERE ARE TWO BUILDINGS TO BE
 CONSIDERED: THE CABANA AND THE MAIN
 HOUSE. THEREFORE, IT SHALL BE TWO
 SEPARATE FORMS WITH THEIR RESPECTIVE
 MEAN ROOF HEIGHT.
 3-PROVIDE STRUCTURAL BUCK DETAIL USING
 2X4 BUCK AS REQUIRED BY THE PRODUCT
 APPROVALS FOR DOORS AND WINDOWS.
 4-REVISE FRAMING DETAIL FOR INSTALLATION
 OF OVAL WINDOW. SEE PRODUCT APPROVAL.
 5-PROVIDE PRODUCT APPROVAL FOR:
 -METAL ROOF SYSTEM.
 -TACK ROOM DOUBLE DOORS. OR REVISE
 DRAWINGS SHOWING OVERHEAD DOORS.
 -FRENCH DOORS AS SHOWN ON ARCHITECTURAL
 DRAWINGS. (THREE PANELS)
 -ENTRY DOOR WITH SIDELITES ASSEMBLY.
 -SINGLE SWING DOOR (GARAGE SIDE DOOR).
 6-OWNER TO SIGN AND DATE THE ENERGY
 CALCULATIONS (CABANA AND MAIN HOUSE).
 7-NEED TO FILE NOTICE OF COMMENCEMENT.