Plan Review Notes
Plan Review Notes For Permit 01030199
Permit Number 01030199
Review Stop E
Sequence Number 1
Notes
Date Text
2001-04-02 00:00:00****************** UNSAT *************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 3)NOTE: PLEASE NOTE GFI PROTECTION OF
 OUTLETS 6` FROM SINK IN TACK ROOM PER
 LOCAL AMENDMENT.210-8
  
 4)NOTE: PLEASE NOTE THAT PLAN ONLY SHOWS
 ONE DISCONNECT NEXT TO METERCAN.
  
 5)NOTE: PLEASE NOTETHAT ALL CIRCUITS
 FOR CABANA ARE SHOWN COMING FROM PANEL
 IN MAIN HOUSE? THIS IS NOT PERMITTED.
 225-31 NEC. ALSO PLEASE NOTE GROUNDING
 IS TO BE SHOWN AT DETACHED STRUCTURE
 PER 250-32 AND 250-50.
  
 6)NOTE: PLEASE NOTE THAT PLANS SHOW #8
 FROM DISC "B" TO PANEL "B" WHICH IS
 SHOWN AT 100A.#8 IS NOT RATED FOR 100A.
  
 7)NOTE: PLEASE NOTE PANEL"B" IS SHOWN AT
 100AMPS ANDHAS 142AMP LOAD????
 PLEASE CORRECT. PLEASE CORRELATE WIRE
 SIZE WITH OVERCURRENT PROTECTION
 PROVIDED.SIZE PER 310-16/ 310-15B-6
  
 8)NOTE: PLEASE NOTE SMOKE DETECTOR REQ`D
 INSIDE CABANA PER NFPA-72 2-2.1.1.1
  
 9)NOTE: PLEASE SHOW CONDUCTOR SIZES FROM
 MAIN DISCONNECT TO PANELS AND CONDUIT
 SIZES,EQUIPMENT GROUNDING CONDUCTORS PER
 215-5 AND 250-122.
  
 10)NOTE: PLEASE CLARIFY FEEDS COMING
 INTO METERCAN? PLANS SHOW IN TWO
 LOCATIONS 3-3/0`S IN A 2" CONDUIT? ARE
 THESE PARALELL CONDUITS? PLEASE CLARIFY.
  
 11)NOTE: PLEASE NOTE THAT NO LOAD
 CALCULATIONS WERE SUBMITTED. PLEASE
 SUBMIT LOAD CALCS PER 215-5.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASECALL.