Text |
| 2001-04-02 00:00:00 | ****************** UNSAT ************* |
| | |
| | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | |
| | 2) NOTE: PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S) PER 210-11-C-3. |
| | MUST BE 20A AND #12AWG. |
| | |
| | 3)NOTE: PLEASE NOTE GFI PROTECTION OF |
| | OUTLETS 6` FROM SINK IN TACK ROOM PER |
| | LOCAL AMENDMENT.210-8 |
| | |
| | 4)NOTE: PLEASE NOTE THAT PLAN ONLY SHOWS |
| | ONE DISCONNECT NEXT TO METERCAN. |
| | |
| | 5)NOTE: PLEASE NOTETHAT ALL CIRCUITS |
| | FOR CABANA ARE SHOWN COMING FROM PANEL |
| | IN MAIN HOUSE? THIS IS NOT PERMITTED. |
| | 225-31 NEC. ALSO PLEASE NOTE GROUNDING |
| | IS TO BE SHOWN AT DETACHED STRUCTURE |
| | PER 250-32 AND 250-50. |
| | |
| | 6)NOTE: PLEASE NOTE THAT PLANS SHOW #8 |
| | FROM DISC "B" TO PANEL "B" WHICH IS |
| | SHOWN AT 100A.#8 IS NOT RATED FOR 100A. |
| | |
| | 7)NOTE: PLEASE NOTE PANEL"B" IS SHOWN AT |
| | 100AMPS ANDHAS 142AMP LOAD???? |
| | PLEASE CORRECT. PLEASE CORRELATE WIRE |
| | SIZE WITH OVERCURRENT PROTECTION |
| | PROVIDED.SIZE PER 310-16/ 310-15B-6 |
| | |
| | 8)NOTE: PLEASE NOTE SMOKE DETECTOR REQ`D |
| | INSIDE CABANA PER NFPA-72 2-2.1.1.1 |
| | |
| | 9)NOTE: PLEASE SHOW CONDUCTOR SIZES FROM |
| | MAIN DISCONNECT TO PANELS AND CONDUIT |
| | SIZES,EQUIPMENT GROUNDING CONDUCTORS PER |
| | 215-5 AND 250-122. |
| | |
| | 10)NOTE: PLEASE CLARIFY FEEDS COMING |
| | INTO METERCAN? PLANS SHOW IN TWO |
| | LOCATIONS 3-3/0`S IN A 2" CONDUIT? ARE |
| | THESE PARALELL CONDUITS? PLEASE CLARIFY. |
| | |
| | 11)NOTE: PLEASE NOTE THAT NO LOAD |
| | CALCULATIONS WERE SUBMITTED. PLEASE |
| | SUBMIT LOAD CALCS PER 215-5. |
| | |
| | PLEASE SUBMIT ALL THE ABOVE INFORMATION |
| | FOR REVIEW. IF THERE ARE ANY QUESTIONS |
| | PLEASECALL. |