| Plan Review Notes For Permit 01030153 |
| Permit Number |
01030153 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-03-12 00:00:00 | ****************** UNSAT ************** | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 2) NOTE: PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S) PER 210-11-C-3. | | | MUST BE 20A AND #12AWG. | | | | | | | | | 3)NOTE:PLEASE NOTE, THAT PER 220-3-C1, | | | NEED TO SUBMIT LOAD CALCULATIONS FOR | | | EXISTING SERVICE WITH NEW SERVICE LOAD | | | ADDED. | | | | | | 4)NOTE: PLEASE NOTE NO GROUNDING SYSTEM | | | IS HOWN FOR DETACHED HOUSE. | | | NOTE: PLEASE SHOW GROUNDING | | | ELECTRODEGOING TO BUILDING STEEL AND | | | COLD WATER | | | PER 250-50. | | | | | | 5)NOTE: PLEASE CLARIFY LOAD SHOWN FOR | | | PANEL IN GUEST HOUSE. LOAD SHOWN | | | EXCEEDSSUB FEED OF 60AMPS. SHEET A-2 | | | SHOWS 60A SUBFEED AND A-4 SHOWS 80A ?? | | | PLEASE | | | CALRIFY. | | | | | | | | | PLEASE PUT ELECTRICAL DETAILS ON SAME | | | SHEET. PLEASE SUBMIT THE ABOVE | | | INFORMATION FOR REVIEW. IF THERE ARE | | | ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|