2001-03-12 00:00:00****************** UNSAT **************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
  
 3)NOTE:PLEASE NOTE, THAT PER 220-3-C1,
 NEED TO SUBMIT LOAD CALCULATIONS FOR
 EXISTING SERVICE WITH NEW SERVICE LOAD
 ADDED.
  
 4)NOTE: PLEASE NOTE NO GROUNDING SYSTEM
 IS HOWN FOR DETACHED HOUSE.
 NOTE: PLEASE SHOW GROUNDING
 ELECTRODEGOING TO BUILDING STEEL AND
 COLD WATER
 PER 250-50.
  
 5)NOTE: PLEASE CLARIFY LOAD SHOWN FOR
 PANEL IN GUEST HOUSE. LOAD SHOWN
 EXCEEDSSUB FEED OF 60AMPS. SHEET A-2
 SHOWS 60A SUBFEED AND A-4 SHOWS 80A ??
 PLEASE
 CALRIFY.
  
  
 PLEASE PUT ELECTRICAL DETAILS ON SAME
 SHEET. PLEASE SUBMIT THE ABOVE
 INFORMATION FOR REVIEW. IF THERE ARE
 ANY QUESTIONS PLEASE CALL.
  