| 2002-05-07 00:00:00 | **************** UNSAT **************** |
| | |
| | 1)NOTE: PLEASE NOTE THAT A NOTE FROM |
| | PREVIOUS TWO REVIEWS HAS NOT BEEN |
| | ADDRESSED AND STILLS SHOWS UP ON PLANS?? |
| | PLEASE NOTE IF PLANS ARE SUBMITTED FOR |
| | THE THIRD TIME FOR THE SAME COMMENTS |
| | AND THEY ARE NOT ADDRESS, UNDER 553-80 |
| | OF THE FS/FAC, PLANS CAN BE SUBJECT TO |
| | A 4X THE PLAN REVIEW/REVISION FEE. |
| | PLEASE NOTE THAT A PANEL SCHEDULE WAS |
| | NOT SUBMITTED THIS TIME TO VERIFY THE |
| | SAME CIRCUITS AS ASK FOR ON THE OTHER |
| | REVIEWS. |
| | |
| | 2)NOTE: PLEASE NOTE THAT PLANS ARE NOW |
| | BEING SUBMITTED FOR ADDING TWO NEW |
| | 1600A SERVICES. PLEASE NOTE THAT ALL |
| | REQ`MENTS OF 230-2 WOULD NEED TO BE MET |
| | AND PLANS ARE COMPLETE ENOUGHT FOR THAT. |
| | PLEASE ALSO NOTE THAT PLANS ARE SHOWING |
| | NEW OVER HEAD FEEDS WHICH SHOWS MORETHAN |
| | 8'FT OF UNPROTECTED CONDUCTORS INSIDE |
| | THE BLDG. THIS IS NOT PERMITTED PER |
| | LOCAL AMENDMENTS 230-70 |
| | |
| | 3)NOTE:PLEASE ALSO NOTE THAT A COMPLETE |
| | 2HR SEPARATION WOULD BE NEEDED BETWEEN |
| | EXISTING BLDG AND NEW ELECTRICAL ROOM |
| | WITH A SEPARATE FEED FROM FPL IF A |
| | SECOND SERVICE WAS PERMITTED TO THE SAME |
| | BLDG. |
| | |
| | 4)NOTE: PLEASE NOTE GROUPING OF MAINS |
| | PER 230-72. IDENTIFICATION PER 230-2E |
| | |
| | 5)NOTE:PLEASE NOTE THAT SERVICE ENTRANCE |
| | CONDUCTORS DO NOT MEET 240-3C. 310-16 |
| | 110-14C |
| | |
| | 6)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |