Plan Review Notes
Plan Review Notes For Permit 01030147
Permit Number 01030147
Review Stop M
Sequence Number 7
Notes
Date Text
2001-09-21 00:00:00******************PROVISO***************
  
  
 1.SUBMITTAL OF VENTILATION OF PRIVATE
 PARKING GARAGE SPACES DOES NOT ADDRESS
 AN EMERGENCY POWER SEQUENCE.PLEASE
 PROVIDE APPROPRIATE PLANS TO COMPLY
 WITH ELECTRICAL, FIRE AND MECHCANICAL
 FOR EMERGENCY POWER SITUATION. (SUBMIT
 PRIOR TO ROUGH INSPECTION OF GARAGE.)
  
  
 2.SEQUENCE OF OPERATION & TEST CRITERIA
 AS NOT BEEN SUBMITTED FOR REVIEW.
 (SUBMIT PRIOR FINAL INSPECTIONS.)
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096 EXT.
 8388.