| 2001-11-05 00:00:00 | **************** UNSAT ************* | | | | | | 1)NOTE: PLEASE NOTE THAT OUTLETS SHOWN | | | ON E.1.2.1 ARE SHOWN AS 2-POLE AND NOTED | | | AS 208V 3-PHASE AND 30AMPS? PLEASE NOTE | | | THAT PANEL SCHEDULES SHOW AS 1-POLE | | | 20AMP OUTLETS. | | | CIRCUITS ARE SHOWN AS 2-POLE? | | | | | | PLEASE CLARIFY AND CORRECT. PLEASE | | | SUBMIT FOR REVIEW. | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|