| 2001-08-29 00:00:00 | RE: INFORMATION INCLUDED WITH |
| | TRANSMITTAL LETTER DATED 8/28/01 BCBE |
| | CONSTRUCTION FROM STUART FALKNOR AND |
| | THESTH LETTER DATED 8/13/01 TITLED |
| | "THIRD |
| | PLAN REVIEW" COMMENTS. |
| | |
| | TILE ROOF ASSEMBLY NOA 99-1102.04 IS FOR |
| | A WOOD DECK ASSEMBLY. TESTING IS |
| | REQUIRED FOR THE "DENS DECK" |
| | APPLICATION IF THAT IS THE INTENDED |
| | PURPOSE OF THE CATALOG SHEET COPIES |
| | PROVIDED. |
| | |
| | THE GAF NOA 00-0331.10 IS MISSING THE |
| | PAGES CONTAINING THE DESIGN WIND |
| | PRESSURE AND THE LIMITATIONS. |
| | |
| | THE ABOVE ITEMS CAN BE PROVISIONALLY |
| | ACCEPTED. |
| | |
| | NEW SHEET A.2.2.1 CITES 1999 STANDARD |
| | BUILDING CODE.AS STATED IN THE |
| | EARLIER REVIEW COMMENTS, THE CITY |
| | CURRENTLY INVOKES THE 1997 EDITION. |
| | |
| | THE STH RESPONSE TO ITEM #6 "THE |
| | CALCULATED GARAGE AREA FOR EXHAUSTING |
| | DOES NOT INCLUDED THE PRIVATE GARAGES, |
| | AS THEY ARE CONDITIONED SPACES." IS OK |
| | AS LONG IT IS DEMONSTRATED THAT THE |
| | "CONDITIONED AIR" IS EXCHANGED AT THE |
| | RATE OF AT LEAST SIX TIMES PER HOUR IN |
| | ACCORDANCE WITH SBC 411.4.2,1997. |
| | |
| | THE SPECIFICATION SHEETS PROVIDED HAVE |
| | CONFUSING WIND DESIGN INFORMATION AND |
| | SPECIFICATION 08520 FIXED ALUMINUM |
| | WINDOWS, DOES NOT ADDRESS HURRICANE |
| | MISSILE IMPACT RESISTANCE.THE WIND |
| | PRESSURES ARE THOSE SET OUT IN THE WIND |
| | TUNNEL TESTING THAT THE BUILDING WAS |
| | DESIGNED TO.THE MISSILE IMPACT |
| | TESTING MUST MEET SSTD 12-97 OR HAVE A |
| | CURRENT DADE COUNTY ACCEPTANCE REPORT. |