Plan Review Notes
Plan Review Notes For Permit 01030147
Permit Number 01030147
Review Stop B
Sequence Number 5
Notes
Date Text
2001-08-29 00:00:00RE: INFORMATION INCLUDED WITH
 TRANSMITTAL LETTER DATED 8/28/01 BCBE
 CONSTRUCTION FROM STUART FALKNOR AND
 THESTH LETTER DATED 8/13/01 TITLED
 "THIRD
 PLAN REVIEW" COMMENTS.
  
 TILE ROOF ASSEMBLY NOA 99-1102.04 IS FOR
 A WOOD DECK ASSEMBLY. TESTING IS
 REQUIRED FOR THE "DENS DECK"
 APPLICATION IF THAT IS THE INTENDED
 PURPOSE OF THE CATALOG SHEET COPIES
 PROVIDED.
  
 THE GAF NOA 00-0331.10 IS MISSING THE
 PAGES CONTAINING THE DESIGN WIND
 PRESSURE AND THE LIMITATIONS.
  
 THE ABOVE ITEMS CAN BE PROVISIONALLY
 ACCEPTED.
  
 NEW SHEET A.2.2.1 CITES 1999 STANDARD
 BUILDING CODE.AS STATED IN THE
 EARLIER REVIEW COMMENTS, THE CITY
 CURRENTLY INVOKES THE 1997 EDITION.
  
 THE STH RESPONSE TO ITEM #6 "THE
 CALCULATED GARAGE AREA FOR EXHAUSTING
 DOES NOT INCLUDED THE PRIVATE GARAGES,
 AS THEY ARE CONDITIONED SPACES." IS OK
 AS LONG IT IS DEMONSTRATED THAT THE
 "CONDITIONED AIR" IS EXCHANGED AT THE
 RATE OF AT LEAST SIX TIMES PER HOUR IN
 ACCORDANCE WITH SBC 411.4.2,1997.
  
 THE SPECIFICATION SHEETS PROVIDED HAVE
 CONFUSING WIND DESIGN INFORMATION AND
 SPECIFICATION 08520 FIXED ALUMINUM
 WINDOWS, DOES NOT ADDRESS HURRICANE
 MISSILE IMPACT RESISTANCE.THE WIND
 PRESSURES ARE THOSE SET OUT IN THE WIND
 TUNNEL TESTING THAT THE BUILDING WAS
 DESIGNED TO.THE MISSILE IMPACT
 TESTING MUST MEET SSTD 12-97 OR HAVE A
 CURRENT DADE COUNTY ACCEPTANCE REPORT.