Date Text
2001-11-10 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97 - SGC-97
 RE: SUBMITTALS
  
 1) SPECIFICATION(S) 15120P.2.05A AIR
 CHAMBERS NOT APPROVED AS SUBMITTED.
 SUBMIT INFORMATION ON ACCESS PANELS AND
 SHOW COMPLIANCE WITH WH-PDI 201, SHOW
 HOW AIR CHAMBERS WILL BE RECHARGEALBE.
 SPC SEC 607.8.3
 2) SPECIFICATIONS(S) 15160P, 15160P.2.01
 AND 15160P.2.04, SHOW LISTING FOR EACH
 PUMP SUBMITTED.
 3) PLEASE PROVIDE NSF APPROVAL FOR ALL
 VALVES.
 4) EXPANSION TANK MANUFACTURE SHEETS AND
 APPROVAL REQUIRED.
 5) MORE INFORMATION REQUIRED FOR HEAT
 EXCHANGER.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377