Plan Review Notes
Plan Review Notes For Permit 01030147
Permit Number 01030147
Review Stop M
Sequence Number 4
Notes
Date Text
2001-08-10 00:00:00******************PROVISO***************
  
  
 1.PLEASE ADD NOTE TO HEAT PUMP
 SCHEDULE THAT HEAT PUMPS IN "PRIVATE
 GARAGE"SHALL BE CONTROLLED BY
 A HUMIDISTAT NOT A THERMOSTAT.
  
 2.ALL CALCULATIONS SUBMITTED BY
 WADSWORTH ENGINEERING MUST BE
 SEALED, SIGNED AND DATED.
  
 3.PLEASE SUBMIT TEST CRITERIA FOR
 STAIRWELL PRESSURIZATION.
  
 4.PLEASE PROVIDE DETIAL SHOWING
 COMPLIANCE WITH 1997 SMC 405, AIR
 INTAKE SHALL NOT BE LOCATED CLOSER
 THAN 10' FROM ANY SANITARY VENT
 UNLESS SUCH OUTLET IS 24" ABOVE AIR
 INTAKE.SHOULD EXHAUST AND SUPPLY
 NOT HAVE THIS DISTANCE SEF-7 SHALL
 INTERLOCK TO SHUTDOWN UPON
 ACTIVATION OF SSF-1.
  