Plan Review Notes
Plan Review Notes For Permit 01030147
Permit Number 01030147
Review Stop B
Sequence Number 4
Notes
Date Text
2001-08-15 00:00:00SEE PREVIOUS CHECKLIST DATED 7/17/01.
  
 THE NOTICE OF ACCEPTANCE REPORT
 #99-0204.07 FOR THE WINDOW WALL SYSTEM
 DOES NOT HAVE THE COMPONENTS MARKED OR
 THEIR LOCATIONS TO BE INSTALLED IN THE
 BUILDING.
  
 NOA 99-0505.08 DOORS IS NOT MARKED.
  
 NOA 01-0129.09 STEEL DOOR.SAME.
  
 NO CHANGE TO SPECIFICATION RE: WIND
 DESIGN REQUIREMENTS.
  
 PRESSURIZED STAIR CALCULATIONS UNCHANGED
 GARAGE SMOKE REMOVAL RE: VOLUME AND
 PRIVATE GARAGES NOT ADDRESSED FROM
 PREVIOUS CHECKIST.
  
 IN SUMMARY.DEMONSTRATE COMPLIANCE WITH
 SBC 412.6 #5 FOR THE STAIRS.SBC
 412.5#3 FOR THE ELEVATOR LOBBY AREA.
 PROVIDE CURRENT TEST REPORTS FOR THE
 DOORS, WINDOWS, AND ROOF COVERINGS
 TOGETHER WITH THE INFORMATION REQUIRED
 THAT IS CONTAINED WITHIN THOSE REPORTS.