| Plan Review Notes For Permit 01030147 |
| Permit Number |
01030147 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2001-08-15 00:00:00 | SEE PREVIOUS CHECKLIST DATED 7/17/01. | | | | | | THE NOTICE OF ACCEPTANCE REPORT | | | #99-0204.07 FOR THE WINDOW WALL SYSTEM | | | DOES NOT HAVE THE COMPONENTS MARKED OR | | | THEIR LOCATIONS TO BE INSTALLED IN THE | | | BUILDING. | | | | | | NOA 99-0505.08 DOORS IS NOT MARKED. | | | | | | NOA 01-0129.09 STEEL DOOR.SAME. | | | | | | NO CHANGE TO SPECIFICATION RE: WIND | | | DESIGN REQUIREMENTS. | | | | | | PRESSURIZED STAIR CALCULATIONS UNCHANGED | | | GARAGE SMOKE REMOVAL RE: VOLUME AND | | | PRIVATE GARAGES NOT ADDRESSED FROM | | | PREVIOUS CHECKIST. | | | | | | IN SUMMARY.DEMONSTRATE COMPLIANCE WITH | | | SBC 412.6 #5 FOR THE STAIRS.SBC | | | 412.5#3 FOR THE ELEVATOR LOBBY AREA. | | | PROVIDE CURRENT TEST REPORTS FOR THE | | | DOORS, WINDOWS, AND ROOF COVERINGS | | | TOGETHER WITH THE INFORMATION REQUIRED | | | THAT IS CONTAINED WITHIN THOSE REPORTS. |
|