Plan Review Notes For Permit 01030147
Permit Number 01030147
Review Stop M
Sequence Number 3
Notes
Date Text
2001-07-02 00:00:00 
 PLEASE PROVIDE THE FOLLOWING INFORMATION
  
  
 PLEASE PROVIDE SEQUENCE OF OPERATION AS
 WELL AS TEST CRITERIA FOR SMOKE EVAQ.
  
 ENG COMMENTS 6 & 7 POOL HEATERS & FLUE
 VENTS HAVE BEEN ADDED ON DWG M.1.1.1,
 NO SUCH DWG.
  
 MISSING DWGS M.0.0.3, 0.0.4, M.1.1.1, M.
 1.1.4, M.2.0.1, M.2.1.1, M.2.1.2, M.4.1.
 2, M.4.2.1, M.4.3.1.
  
 PLEASE PROVIDE MANUFACTURER DATA FOR
 THE GENERATOR.
  
 NO DETAILS/PLANS FOR COMMON AREAS SUCH A
 AS SPA, LOBBY, MANAGERS OFFICE, BILLIARD
 RM, BOARD RM AND FITNESS RM.
  
 PLEASE PROVIDE A DETAIL FOR SYMBOLS USED
 ON MECHANICAL PLANS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.