Plan Review Notes
Plan Review Notes For Permit 01030147
Permit Number 01030147
Review Stop B
Sequence Number 3
Notes
Date Text
2001-07-17 00:00:00THE PRODUCT TEST REPORTS FOR THE ROOF
 COVERING, WINDOWS AND DOORS HAVE NOT
 BEEN PROVIDED.THE SPECIFICATIONS FOR
 THE WINDOWS AND STOREFRONT SYSTEM CALL
 A 110
 MPH WINDLOAD DESIGN.THIS MUST BE
 CORRECTED TO REFLECT THE RESULTS OF
 THE WIND TUNNEL TESTING.AT NO TIME WAS
 THIS BUILDING CONSIDERED IN A 110 MPH
 WIND ZONE FOR DESIGN PURPOSES.
 NOTE 4 UNDER CODES AND STANDARDS
 CALLS FOR HAND AND GUARD
 RAILS TO BE DESIGNED TO 1608.2.THE
 CODE SECTIONS ARE NOT A SUBSTITUTE FOR
 SPECIFIC INFORMATION.SEE SBC 104.2.
  
 THE STAIR PRESSURE CALCULATIONS ARE NOT
 SIGNED AND SEALED.FURTHER THE
 CALCULATIONS DO NOT CLEARLY INDICATE
 HOW THE BAROMETRIC RELIEF VENTS WILL
 PROVIDE THE 2500 CFM FLOW AS REQUIRED
 BY SBC 412.11 #5 PLEASE CLARIFY AND
 REVISE AS NECESSARY.
  
 SHEET M.5.0.1 SHOWS THE STAIR
 PRESSURIZATION FANS IN CLOSE PROXIMITY
 TO THE LOBBY AND OTHER EXHAUST FANS.
  
 HOW WILL THE CALCULATED GARAGE EXHAUST
 ACCOMMODATE THE "PRIVATE AIR
 CONDITIONED GARAGES WITH THEIR DOORS
 CLOSED?
  
 THE ARCHITECT PLANS SHEET A.1.1.1 CALL
 OUT A 14' CEILING HEIGHT AND 698080 SF
 IN AREA.THE WADSWORTH CALCULATIONS
 NOTE AN 11' CEILING HEIGHT AND 53017 SF
 FLOOR AREA.PLEASE JUSTIFY THE
 DIFFERENCES.NOTE TOO, ALL INFORMATION
 PREPARED BY AN ARCHITECT OR AN ENGINEER
 AND SUBMITTED FOR PUBLIC RECORD, ARE
 REQUIRED TO HAVE THE EMBOSSED SEAL,
 SIGNATURE AND DATE.