| 2001-07-17 00:00:00 | THE PRODUCT TEST REPORTS FOR THE ROOF |
| | COVERING, WINDOWS AND DOORS HAVE NOT |
| | BEEN PROVIDED.THE SPECIFICATIONS FOR |
| | THE WINDOWS AND STOREFRONT SYSTEM CALL |
| | A 110 |
| | MPH WINDLOAD DESIGN.THIS MUST BE |
| | CORRECTED TO REFLECT THE RESULTS OF |
| | THE WIND TUNNEL TESTING.AT NO TIME WAS |
| | THIS BUILDING CONSIDERED IN A 110 MPH |
| | WIND ZONE FOR DESIGN PURPOSES. |
| | NOTE 4 UNDER CODES AND STANDARDS |
| | CALLS FOR HAND AND GUARD |
| | RAILS TO BE DESIGNED TO 1608.2.THE |
| | CODE SECTIONS ARE NOT A SUBSTITUTE FOR |
| | SPECIFIC INFORMATION.SEE SBC 104.2. |
| | |
| | THE STAIR PRESSURE CALCULATIONS ARE NOT |
| | SIGNED AND SEALED.FURTHER THE |
| | CALCULATIONS DO NOT CLEARLY INDICATE |
| | HOW THE BAROMETRIC RELIEF VENTS WILL |
| | PROVIDE THE 2500 CFM FLOW AS REQUIRED |
| | BY SBC 412.11 #5 PLEASE CLARIFY AND |
| | REVISE AS NECESSARY. |
| | |
| | SHEET M.5.0.1 SHOWS THE STAIR |
| | PRESSURIZATION FANS IN CLOSE PROXIMITY |
| | TO THE LOBBY AND OTHER EXHAUST FANS. |
| | |
| | HOW WILL THE CALCULATED GARAGE EXHAUST |
| | ACCOMMODATE THE "PRIVATE AIR |
| | CONDITIONED GARAGES WITH THEIR DOORS |
| | CLOSED? |
| | |
| | THE ARCHITECT PLANS SHEET A.1.1.1 CALL |
| | OUT A 14' CEILING HEIGHT AND 698080 SF |
| | IN AREA.THE WADSWORTH CALCULATIONS |
| | NOTE AN 11' CEILING HEIGHT AND 53017 SF |
| | FLOOR AREA.PLEASE JUSTIFY THE |
| | DIFFERENCES.NOTE TOO, ALL INFORMATION |
| | PREPARED BY AN ARCHITECT OR AN ENGINEER |
| | AND SUBMITTED FOR PUBLIC RECORD, ARE |
| | REQUIRED TO HAVE THE EMBOSSED SEAL, |
| | SIGNATURE AND DATE. |