| Plan Review Notes For Permit 01030147 |
| Permit Number |
01030147 |
|
| Review Stop |
M |
| Sequence Number |
27 |
|
| Notes |
| Date |
Text |
| 2003-04-09 00:00:00 | PROVIDE THE FOLLOWING INFORMATION: | | | | | | 1.WHAT IS BEING STORED IN THE "POOL | | | STORAGE" & "POOL EQUIPMENT" ROOMS. | | | | | | 2.CLARIFY WERE THE EXHAUST LOUVER | | | WILL BE DISCHARGING THE AIR FROM THESE | | | ROOMS (IN THE GARAGE, WALKWAY OR TO THE | | | OUTSIDE). | | | | | | 3.DOES THIS ROOM HAVE A FIRE RATING? | | | | | | 4.SUBMITTAL FOR SUPPLY FAN SF-3 (ROOM | | | #?) - WHAT IS THIS ROOM TO BE USED FOR? | | | IS THIS ROOM FIRE RATED? PLEASE NOTE | | | FIRE DAMPER IS INDICATED ON DUCT RUNNING | | | THROUGH THIS SPACE. |
|