| 2003-02-26 00:00:00 | **************** UNSAT ************* | | | PH-3 | | | 1)NOTE: PLEASE SEE PANEL SCHEDULE FOR | | | F1, PLEASE CORRELATE LOADS FOR SUB | | | PANELS F2 AND F3. | | | | | | 2)NOTE: PLEASE SEE LOADS ON 15A BRKRS | | | LOADS EXCEED 80%, PLEASE CLARIFY IF | | | LOADS THAT ARE ON 20A CIRCUITS, SHOWN AS | | | 1440 ARE SWITCHED WITH 15A CIRCUTIS?? | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IFTHERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|