| Plan Review Notes For Permit 01030147 |
| Permit Number |
01030147 |
|
| Review Stop |
P |
| Sequence Number |
21 |
|
| Notes |
| Date |
Text |
| 2003-04-08 00:00:00 | REVISION DENIED | | | REFERENCE: FBC-2001 BUILDING | | | | | | 1) REVISION STATES THAT DRAINS & EMER- | | | GENCY OVERFLOW DRAINS ARE VERTICAL, BUT | | | DRAWINGS INDICATE THAT THE DRAINS & OVER | | | FLOWS ARE HORIZONTAL. PLEASE CLAIRFY. | | | INDICATE TYPE OF MATERIAL AND SLOPE OF | | | PIPE. | | | 2) DETAILS SUBMITTED WITH REVISION DO | | | NOT INDICATE HEIGHT ABOVE ROOF TO THE | | | INLET FLOW LINE AS REQUIRED IN SECTION | | | 1503.4.2. ALSO SHOW DETAIL FOR ROOF | | | DRAIN INSTALLED SHOWING ALL REQUIRED | | | MEASUREMENTS. | | | 3) ALL DETAILS SHALL BE SIGNED & SEALED | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 | | | (561) 805-6721 | | | FAX (561) 653-2692 |
|