Plan Review Notes
Plan Review Notes For Permit 01030147
Permit Number 01030147
Review Stop P
Sequence Number 2
Notes
Date Text
2001-06-24 00:00:00REVIEW OF PLUMBING COMMENTS 06-06-01
 FROM ARCHITECTURAL GROUP
 (1A) SEE CIVIL DRAWINGS
 (1B) DOCKS ARE STILL REFERENCED ON
 ARCHITCURAL DRAWINGS.
 (1C) FLORIDA PUBLIC UTILITIES TO FURNISH
 GAS PIPING PLAN UP TO POINT OF SERVICE.
 CONTACT MR DAVID PELLICO 561-838-1752
 (2A) SHT P.0.0.1 ALL ABBREVATIONS ON
 PLANS NOT LISTED.
 (2B) SHT P.0.01 DETAIL, ELEVATOR NOT
 DELETED.
 (3) SHT P.1.0.1 CAR WASH INTERCEPTOR
 DRAIN HAS NOT BEEN CORRECTED, CONNECT TO
 SANITARY SEWER.
 (4) SHTS FOR DOMESTIC WATER PLANS HAVE
 NOT BEEN CORRECTED, A MAXIMUM OF 2 PLBG
 FIXTURES ON 1/2" C/W AND 4 ON 1/2" H/W.
 (6) CUT SHT SUBMITTALS TO BE REVIEWED BY
 ARCHITECT PRIOR TO PLUMBING REVIEW.
 (7A) SHT P.1.0.2 BUILDING SANITARY DRAIN
 NOT APPROVED, USE SPC 94 TAB 714.1 SIZE
 (7B) SHT P.2.0.5 DOMESTIC WATER PLAN,
 USE TAB 607,MINIMUM SIZE OF PLBG FIXTURE
 SUPPLY, HOT AND COLD WATER, 1/2".
 (7C) SHT P.2.0.5 LOBBY WATER FEATURE
 POOL, WATER SUPPLY, BACK FLOW PREVENTER
 REQUIRED, SEC 606.
 (8) SHT P.0.0.1, GAS PIPING BEYOND METER
 NOT ADDRESSED,SEE GAS PERMIT APPLICATION
 REQUIRMENTS, ATTACHED. SEC 104.3
 (9,10) SHT P.3.0.6 ROOF DRAINS, SCUPPER
 DRAINS, USE DESIGN CRITERIA,SPC 94 CH 11
 TAB 1108.1,1108.2,1108.3 FIG.1108.4,
 SECONDARY DRAINS 1109 (SCUPPERS) FIG.
 1109.3 RAINFALL RATES.
 APPENDIX "A", TAB A101.2 SIZING TAB.
 SEC 104.3 ISOMETRIC DRWG, SHOW ALL CALCU
 LATIONS,VERTIAL WALLS, UPPER ROOFS.
 (11) FAIR HOUSING ACT REV 98, OPTION "B"
 USED,SHOW LAYOUT OF GRAB BAR REQUIRMENT
 FOR ALL FIXTURES AS REQUIRED.
 ONE OF EACH TYPE OF FIXTURE MUST BE
 USEABLE IN OPTION 'B",BIDET IS INCLUDED.
 (12) SOVENT SYSTEM, AS/ YOUR COMMENT.
 END OF COMMENTSPAUL SCHMITZ
 QUESTIONS561-659-8096X8233