| 2001-06-24 00:00:00 | REVIEW OF PLUMBING COMMENTS 06-06-01 |
| | FROM ARCHITECTURAL GROUP |
| | (1A) SEE CIVIL DRAWINGS |
| | (1B) DOCKS ARE STILL REFERENCED ON |
| | ARCHITCURAL DRAWINGS. |
| | (1C) FLORIDA PUBLIC UTILITIES TO FURNISH |
| | GAS PIPING PLAN UP TO POINT OF SERVICE. |
| | CONTACT MR DAVID PELLICO 561-838-1752 |
| | (2A) SHT P.0.0.1 ALL ABBREVATIONS ON |
| | PLANS NOT LISTED. |
| | (2B) SHT P.0.01 DETAIL, ELEVATOR NOT |
| | DELETED. |
| | (3) SHT P.1.0.1 CAR WASH INTERCEPTOR |
| | DRAIN HAS NOT BEEN CORRECTED, CONNECT TO |
| | SANITARY SEWER. |
| | (4) SHTS FOR DOMESTIC WATER PLANS HAVE |
| | NOT BEEN CORRECTED, A MAXIMUM OF 2 PLBG |
| | FIXTURES ON 1/2" C/W AND 4 ON 1/2" H/W. |
| | (6) CUT SHT SUBMITTALS TO BE REVIEWED BY |
| | ARCHITECT PRIOR TO PLUMBING REVIEW. |
| | (7A) SHT P.1.0.2 BUILDING SANITARY DRAIN |
| | NOT APPROVED, USE SPC 94 TAB 714.1 SIZE |
| | (7B) SHT P.2.0.5 DOMESTIC WATER PLAN, |
| | USE TAB 607,MINIMUM SIZE OF PLBG FIXTURE |
| | SUPPLY, HOT AND COLD WATER, 1/2". |
| | (7C) SHT P.2.0.5 LOBBY WATER FEATURE |
| | POOL, WATER SUPPLY, BACK FLOW PREVENTER |
| | REQUIRED, SEC 606. |
| | (8) SHT P.0.0.1, GAS PIPING BEYOND METER |
| | NOT ADDRESSED,SEE GAS PERMIT APPLICATION |
| | REQUIRMENTS, ATTACHED. SEC 104.3 |
| | (9,10) SHT P.3.0.6 ROOF DRAINS, SCUPPER |
| | DRAINS, USE DESIGN CRITERIA,SPC 94 CH 11 |
| | TAB 1108.1,1108.2,1108.3 FIG.1108.4, |
| | SECONDARY DRAINS 1109 (SCUPPERS) FIG. |
| | 1109.3 RAINFALL RATES. |
| | APPENDIX "A", TAB A101.2 SIZING TAB. |
| | SEC 104.3 ISOMETRIC DRWG, SHOW ALL CALCU |
| | LATIONS,VERTIAL WALLS, UPPER ROOFS. |
| | (11) FAIR HOUSING ACT REV 98, OPTION "B" |
| | USED,SHOW LAYOUT OF GRAB BAR REQUIRMENT |
| | FOR ALL FIXTURES AS REQUIRED. |
| | ONE OF EACH TYPE OF FIXTURE MUST BE |
| | USEABLE IN OPTION 'B",BIDET IS INCLUDED. |
| | (12) SOVENT SYSTEM, AS/ YOUR COMMENT. |
| | END OF COMMENTSPAUL SCHMITZ |